Table 5:
Function of selections
Selection
Function
S1
Activates the Base Model Database. The table of Bay Models (S4) containing the
BM’s created by ABB can be selected.
S2
Activates the User Model Database. The table of Bay Models (S4) containing the
BM’s created by the user (client) can be selected.
S3
If the option Filter Selection by Bay Model type is selected, the table of Bay
Models (S4) is filtered according the BM type. The filter criteria (number of
busbars) is automatically derived from the Plant data settings (see
If this option is not selected, all models of the respective database are visible.
S4
Table of bay models à The content of this table is controlled by the buttons S1-S3.
By selecting one of the table lines with a left mouse click, a BM is selected
(highlighted in blue colour) for import to the single-line diagram.
After pressing the button OK or Apply, the menu Import options appears for the
selected BM (see
).
Table 6:
Indications
Selection
Function
V1
Single-line diagram of the selected BM → Selection made under S4
V2
Description of the selected BM → Selection made under S4
Example:
2SSF5A1
BBP,BFP
2 x single Pole
double busbar, F5A1→ BM identifier
Station protection functions contained in the BM
Tripping outputs configured in the BM → two sets of
single pole trip-ping contacts (2 x 3)
5.5.4
Import options
GUID-27683D70-F7C5-482C-8808-52E05B7522AF v2
See
This menu appears, if under the menu Select bay Model (see
), the button OK or Apply
is pressed. Now, the import-options of the BM can be selected by the user.
15000008-IEC18000615-1-en.vsdx
IEC18000615 V1 EN-US
Figure 9:
BM import options
1MRK 511 452-UUS Rev. A
Section 5
Configuration
Distributed busbar protection REB500
25
Engineering manual