The BLOCK signal is a general purpose blocking signal of the pole discrepancy
protection. It can be connected to a binary input in the IED in order to receive a block
command from external devices or can be software connected to other internal
functions in the IED itself in order to receive a block command from internal functions.
Through OR gate it can be connected to both binary inputs and internal function outputs.
The BLKDBYAR signal blocks the pole discrepancy operation when a single phase
autoreclosing cycle is in progress. It can be connected to the output signal 1PT1 on
SMBRREC (79) function block. If the autoreclosing function is an external device,
then BLKDBYAR has to be connected to a binary input in the IED and this binary
input is connected to a signalization “1phase autoreclosing in progress” from the
external autoreclosing device.
If the pole discrepancy protection is enabled, then two different criteria can generate a
trip signal TRIP:
•
Pole discrepancy signaling from the circuit breaker.
•
Unsymmetrical current detection.
7.10.2.1
Pole discrepancy signaling from circuit breaker
If one or two poles of the circuit breaker have failed to open or to close the pole
discrepancy status, then the function input EXTPDIND is activated from the pole
discrepancy signal derived from the circuit breaker auxiliary contacts (one NO contact
for each phase connected in parallel, and in series with one NC contact for each phase
connected in parallel) and, after a settable time interval
tTrip
(0-60 s), a 150 ms trip
pulse command TRIP is generated by the Polediscrepancy function (52PD).
7.10.2.2
Unsymmetrical current detection
Unsymmetrical current indicated if:
•
any phase current is lower than
CurrUnsymPU
of the highest current in the three
phases.
•
the highest phase current is greater than
CurrRelPU
of
IBase
.
If these conditions are true, an unsymmetrical condition is detected and the internal
signal INPS is turned high. This detection is enabled to generate a trip after a set time
delay
tTrip
if the detection occurs in the next 200 ms after the circuit breaker has
received a command to open trip or close and if the unbalance persists. The 200 ms
limitation is for avoiding unwanted operation during unsymmetrical load conditions.
The pole discrepancy protection is informed that a trip or close command has been
given to the circuit breaker through the inputs CLOSECMD (for closing command
Section 7
1MRK505222-UUS C
Current protection
468
Technical reference manual
Содержание Relion 670 series
Страница 1: ...Relion 670 series Line differential protection RED670 ANSI Technical reference manual...
Страница 2: ......
Страница 40: ...34...
Страница 50: ...44...
Страница 60: ...54...
Страница 126: ...120...
Страница 384: ...378...
Страница 496: ...490...
Страница 556: ...550...
Страница 602: ...596...
Страница 620: ...614...
Страница 794: ...788...
Страница 864: ...858...
Страница 988: ...982...
Страница 998: ...992...
Страница 1084: ...1078...
Страница 1164: ...1158...
Страница 1168: ...1162...
Страница 1170: ...1MRK002802 AB 1 670 1 2 PG ANSI V1 EN Section 21 1MRK505222 UUS C Connection diagrams 1164 Technical reference manual...
Страница 1171: ...1MRK002802 AB 2 670 1 2 PG ANSI V1 EN 1MRK505222 UUS C Section 21 Connection diagrams 1165 Technical reference manual...
Страница 1172: ...1MRK002802 AB 3 670 1 2 PG ANSI V1 EN Section 21 1MRK505222 UUS C Connection diagrams 1166 Technical reference manual...
Страница 1173: ...1MRK002802 AB 4 670 1 2 PG ANSI V1 EN 1MRK505222 UUS C Section 21 Connection diagrams 1167 Technical reference manual...
Страница 1174: ...1MRK002802 AB 5 670 1 2 ANSI V1 EN Section 21 1MRK505222 UUS C Connection diagrams 1168 Technical reference manual...
Страница 1175: ...1MRK002802 AB 6 670 1 2 ANSI V1 EN 1MRK505222 UUS C Section 21 Connection diagrams 1169 Technical reference manual...
Страница 1176: ...1MRK002802 AB 7 670 1 2 ANSI V1 EN Section 21 1MRK505222 UUS C Connection diagrams 1170 Technical reference manual...
Страница 1177: ...1MRK002802 AB 8 670 1 2 ANSI V1 EN 1MRK505222 UUS C Section 21 Connection diagrams 1171 Technical reference manual...
Страница 1178: ...1MRK002802 AB 9 670 1 2 ANSI V1 EN Section 21 1MRK505222 UUS C Connection diagrams 1172 Technical reference manual...
Страница 1179: ...1MRK002802 AB 10 670 1 2 ANSI V1 EN 1MRK505222 UUS C Section 21 Connection diagrams 1173 Technical reference manual...
Страница 1180: ...1MRK002802 AB 11 670 1 2 ANSI V1 EN Section 21 1MRK505222 UUS C Connection diagrams 1174 Technical reference manual...
Страница 1181: ...1MRK002802 AB 12 670 1 2 ANSI V1 EN 1MRK505222 UUS C Section 21 Connection diagrams 1175 Technical reference manual...
Страница 1182: ...1MRK002802 AB 13 670 1 2 ANSI V1 EN Section 21 1MRK505222 UUS C Connection diagrams 1176 Technical reference manual...
Страница 1183: ...1MRK002802 AB 14 670 1 2 ANSI V1 EN 1MRK505222 UUS C Section 21 Connection diagrams 1177 Technical reference manual...
Страница 1184: ...1MRK002802 AB 15 670 1 2 ANSI V1 EN Section 21 1MRK505222 UUS C Connection diagrams 1178 Technical reference manual...
Страница 1220: ...1214...
Страница 1230: ...1224...
Страница 1231: ...1225...