IEC99000529-2-en.vsdx
Y
t
Value Reported
(1st)
Value Reported
Value Reported
Y1
Y2
Y3
Y
Y
Y
Y
Y
Y
Value Reported
IEC99000529 V2 EN-US
Figure 192: Magnitude dead-band supervision reporting
After the new value is reported, the ±ΔY limits for dead-band are automatically set around it. The
new value is reported only if the measured quantity changes more than defined by the ±ΔY set
limits.
Integral dead-band reporting
SEMOD54417-167 v4
The measured value is reported if the time integral of all changes exceeds the pre-set limit
(
XDbRepInt), figure
, where an example of reporting with integral dead-band supervision is
shown. The picture is simplified: the process is not continuous but the values are evaluated with a
time interval of one execution cycle from each other.
The last value reported, Y1 in figure
serves as a basic value for further measurement. A
difference is calculated between the last reported and the newly measured value and is multiplied
by the time increment (discrete integral). The absolute values of these integral values are added
until the pre-set value is exceeded. This occurs with the value Y2 that is reported and set as a new
base for the following measurements (as well as for the values Y3, Y4 and Y5).
The integral dead-band supervision is particularly suitable for monitoring signals with small
variations that can last for relatively long periods.
1MRK 502 066-UUS B
Section 7
Impedance protection
365
Technical manual
Содержание Relion 670 series
Страница 1: ... RELION 670 SERIES Generator protection REG670 Version 2 1 ANSI Technical manual ...
Страница 2: ......
Страница 48: ...42 ...
Страница 62: ...56 ...
Страница 182: ...176 ...
Страница 692: ...686 ...
Страница 726: ...720 ...
Страница 1014: ...1008 ...
Страница 1242: ...1236 ...
Страница 1362: ...1356 ...
Страница 1386: ...1380 ...
Страница 1422: ...1416 ...
Страница 1431: ...1425 ...