A substation can be equipped with two redundant authentication servers operating in a hot
standby mode.
•
If configured by the security administrator, the IED itself maintains a local replica in the
database with selected users. This database is periodically updated with data from the server
and used as fallback if none of the servers are reachable.
Note that not all users in the SDM600 server are part of the replica. There might be users that are
not assigned to any replication group. IED only replicates those users which are part of replication
group configured in the IED.
This replication can be disabled using PCM600 by the security administrator, which means that
the IED will forward login requests to the SDM600 for authorization and in case of problems with
the network users will not be able to log in to the IED.
If user replication has been disabled in a CAM-enabled IED and if communication
with SDM600 is lost, access to that IED will be denied until communication is re-
established.
All communication between the central management and the IEDs is protected using secure
communication. Customers using SDM600 are required to generate and distribute certificates
during the engineering process of the substation. These certificates ensure mutual trust between
IED and for example SDM600, FTP, PCM600 and other system.
Table 944: Authority-related IED functions
Function
Description
Authority status
ATHSTAT
This function is an indication function block for user logon activity.
User denied attempt to logon and user successful logon are reported.
Authority check
ATHCHCK
To safeguard the interests of our customers, both the IED and the tools that are
accessing the IED are protected, by means of authorization handling. The authorization
handling of the IED and the PCM600 is implemented at both access points to the IED:
•
local, through the local HMI
•
remote, through the communication ports
The IED users can be created, deleted and edited only in the CAM server.
Authority
management
AUTHMAN
This function enables/disables the maintenance menu. It also controls the maintenance
menu logon time out.
For more information on the functions Authority Management (AUTHMAN), Authority Status
(ATHSTAT), and Authority Check (ATHCHCK) functions, refer to chapter “Basic IED functions” in
the Technical Manual.
20.2
Authority management AUTHMAN
20.2.1
Identification
GUID-7925E6A3-301D-44A5-982F-167805EEA473 v1
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Authority management
AUTHMAN
-
-
Section 20
1MRK 502 066-UUS B
Security
1224
Technical manual
Содержание Relion 670 series
Страница 1: ... RELION 670 SERIES Generator protection REG670 Version 2 1 ANSI Technical manual ...
Страница 2: ......
Страница 48: ...42 ...
Страница 62: ...56 ...
Страница 182: ...176 ...
Страница 692: ...686 ...
Страница 726: ...720 ...
Страница 1014: ...1008 ...
Страница 1242: ...1236 ...
Страница 1362: ...1356 ...
Страница 1386: ...1380 ...
Страница 1422: ...1416 ...
Страница 1431: ...1425 ...