Fault indication
Additional information
Internal Fail
Runtime App Error
One or more of the application threads are not in an expected
state.
Internal Fail
IEC 61850 Error
IEC 61850 has not succeeded in some actions such as reading
the configuration file or start-up.
Internal Fail
DNP3 Error
An error in DNP3 communication has occurred.
Internal Fail
PSM1-Error
A PSM card error has occurred. The instance number is shown
as part of the fault indication, such as 1 in this example.
Internal Fail
BIM3-Error
A binary-in-module error has occurred. The instance number is
shown as part of the fault indication, such as 3 in this example.
Internal Fail
BOM4-Error
A binary-out-module error has occurred. The instance number is
shown as part of the fault indication, such as 4 in this example.
Internal Fail
IOM5-Error
A in/out-module error has occurred. The instance number is
shown as part of the fault indication, such as 5 in this example.
Internal Fail
NUM30-Error
A NUM card error has occurred. The instance number is shown
as part of the fault indication, such as 30 in this example.
Internal Fail
SLM301-Error
A SLM card error has occurred. The instance number is shown
as part of the fault indication, such as 301 in this example.
9.2.2
Warnings
GUID-7BAFA38E-5163-4E01-A7C3-6489B42233C7 v5
The warning message associated with the fault is found in the internal event list in the LHMI
menu Main menu/Diagnostics/Internal events. The message includes the date, time,
description and signal state for the fault. The current status of the internal fault signals can
also be checked via the LHMI in Main menu/Diagnostics/IED status/General.
When a fault appears, record the fault indication message and state it when ordering service.
Table 21: Warning indications
Warning indication
Additional information
Warning
IEC 61850 Error
IEC 61850 has not
succeeded in some actions
such as reading the
configuration file, startup
etc.
Warning
GOOSE Error
One or more access point is
not able to run GOOSE due
to GOOSE being
deactivated on the access
point, or the access point
being deactivated or failing.
Warning
DNP3 Error
Error in DNP3
communication.
9.2.3
Additional indications
GUID-69561C77-50E8-45E2-B8AC-80116222B5B9 v3
The additional indication messages do not activate internal fault or warning.
The messages are listed in the LHMI menu under the event list. The signal status data is found
under the IED status and in the internal event list.
1MRK 500 127-UEN D
Section 9
Troubleshooting
670 series
81