The signal flow between the function blocks is shown in Figure
function, the function blocks Reservation input (RESIN) and Bay reserve (QCRSV) also are
included in the apparatus control function. The application description for all these functions
can be found below. The function SCILO in the Figure below is the logical node for interlocking.
Control operation can be performed from the local IED HMI. If the administrator has defined
users with the IED Users tool in PCM600, then the local/remote switch is under authority
control. If not, the default (factory) user is the SuperUser that can perform control operations
from the local IED HMI without LogOn. The default position of the local/remote switch is on
remote.
en05000116.vsd
SXCBR
SCSWI
SCILO
SXCBR
SXCBR
SCSWI
SCILO
SXSWI
-QA1
-QB1
-QB9
IEC 61850
QCBAY
IEC05000116 V1 EN-US
Figure 325: Signal flow between apparatus control function blocks
Accepted originator categories for PSTO
If the requested command is accepted by the authority, the value will change. Otherwise the
attribute
blocked-by-switching-hierarchy is set in the cause signal. If the PSTO value is
changed during a command, then the command is aborted.
The accepted originator categories for each PSTO value are shown in
Table 47: Accepted originator categories for each PSTO
Permitted Source To Operate
Originator (orCat)
0 = Off
4,5,6
1 = Local
1,4,5,6
Table continues on next page
Section 14
1MRK 505 343-UEN B
Control
552
Application manual
Содержание Relion 670 series
Страница 1: ...RELION 670 SERIES Line differential protection RED670 Version 2 1 IEC Application manual...
Страница 2: ......
Страница 40: ...34...
Страница 64: ...58...
Страница 150: ...144...
Страница 406: ...400...
Страница 472: ...466...
Страница 494: ...488...
Страница 512: ...506...
Страница 524: ...518...
Страница 604: ...598...
Страница 686: ...680...
Страница 718: ...712...
Страница 722: ...716...
Страница 758: ...752...
Страница 759: ...753...