in other products as well. An IED can communicate with
up to 4 remote IEDs.
Binary signal transfer to remote end, 192 signals
M13458-3 v4
If the communication channel is used for transfer of
binary signals only, up to 192 binary signals can be
exchanged between two IEDs. For example, this
functionality can be used to send information such as
status of primary switchgear apparatus or intertripping
signals to the remote IED. An IED can communicate with
up to 4 remote IEDs.
Line data communication module, short and medium
range LDCM
SEMOD168481-4 v7
The line data communication module (LDCM) is used for
communication between the IEDs situated at distances
<60 km/37miles or from the IED to optical to electrical
converter with G.703 or G.703E1 interface located on a
distances < 3 km/1.9 miles away. The LDCM module
sends and receives data, to and from another LDCM
module. The IEEE/ANSI C37.94 standard format is used.
Galvanic X.21 line data communication module X.21-
LDCM
GUID-3C6C7DAC-1DB1-4CB8-991F-3B1D86551F28 v3
A module with built-in galvanic X.21 converter which e.g.
can be connected to modems for pilot wires is also
available.
Galvanic interface G.703 resp G.703E1
M16035-3 v4
The external galvanic data communication converter
G.703/G.703E1 makes an optical-to-galvanic conversion
for connection to a multiplexer. These units are
designed for 64 kbit/s resp 2Mbit/s operation. The
converter is delivered with 19” rack mounting
accessories.
19. Hardware description
Hardware modules
IP14529-1 v1
Power supply module PSM
M11595-3 v5
The power supply module is used to provide the correct
internal voltages and full isolation between the IED and
the battery system. An internal fail alarm output is
available.
Binary input module BIM
M1769-3 v4
The binary input module has 16 optically isolated inputs
and is available in two versions, one standard and one
with enhanced pulse counting capabilities on the inputs
to be used with the pulse counter function. The binary
inputs are freely programmable and can be used for the
input of logical signals to any of the functions. They can
also be included in the disturbance recording and event-
recording functions. This enables extensive monitoring
and evaluation of operation of the IED and for all
associated electrical circuits.
Binary output module BOM
M6938-3 v4
The binary output module has 24 independent output
relays and is used for trip output or any signaling
purpose.
Static binary output module SOM
SEMOD174196-4 v4
The static binary output module has six fast static
outputs and six change over output relays for use in
applications with high speed requirements.
Binary input/output module IOM
M6939-3 v6
The binary input/output module is used when only a few
input and output channels are needed. The ten standard
output channels are used for trip output or any signaling
purpose. The two high speed signal output channels are
used for applications where short operating time is
essential. Eight optically isolated binary inputs cater for
required binary input information.
mA input module MIM
M15020-3 v4
The milli-ampere input module is used to interface
transducer signals in the –20 to +20 mA range from for
example OLTC position, temperature or pressure
transducers. The module has six independent,
galvanically separated channels.
Optical ethernet module OEM
M16073-3 v6
The optical fast-ethernet module is used for fast and
interference-free communication of synchrophasor data
over IEEE C37.118 and/or IEEE 1344 protocols. It is also
used to connect an IED to the communication buses (like
the station bus) that use the IEC 61850-8-1 protocol
(OEM rear port A, B). The process bus use the IEC
61850-9-2LE protocol (OEM rear port C, D). The module
has one or two optical ports with ST connectors.
Serial and LON communication module SLM, supports
SPA/IEC 60870-5-103, LON and DNP 3.0
M14933-3 v4
The serial and LON communication module (SLM) is used
for SPA, IEC 60870-5-103, DNP3 and LON
communication. The module has two optical
communication ports for plastic/plastic, plastic/glass
or glass/glass. One port is used for serial
communication (SPA, IEC 60870-5-103 and DNP3 port)
and one port is dedicated for LON communication.
Line data communication module LDCM
M16075-3 v4
Each module has one optical port, one for each remote
end to which the IED communicates.
Alternative cards for Long range (1550 nm single mode),
Medium range (1310 nm single mode) and Short range
(850 nm multi mode) are available.
Galvanic X.21 line data communication module X.21-LDCM
GUID-D02150FC-54F5-4CE4-8D3D-9F8796B6A527 v3
The galvanic X.21 line data communication module is
used for connection to telecommunication equipment,
for example leased telephone lines. The module
supports 64 kbit/s data communication between IEDs.
1MRK 504 155-BEN F
Transformer protection RET670 2.1 IEC
ABB