IEC13000234-1-en.vsd
GUID-682A59D0-950C-4D89-8318-984E0A8B2761 V1 EN
Figure 30:
Shield connection clamp
The cable shield shall be properly connected to the IED chassis by the
cable clamp with the maximum open conductor length of 40 mm
between clamp and terminals. If double shielded cable is used, the
inner cable shielding should be connected at the external equipment
end only. At the IED terminal end, the inner shield should be isolated.
1MRK514019-UEN A
Section 6
Connecting
670 series 2.0 IEC
55
Installation manual
Содержание Relion 670 2.0 IEC Series
Страница 1: ...Relion Protection and Control 670 series 2 0 IEC Installation manual ...
Страница 2: ......
Страница 10: ...4 ...
Страница 18: ...12 ...
Страница 24: ...18 ...
Страница 42: ...36 ...
Страница 88: ...82 ...
Страница 100: ...94 ...
Страница 109: ...103 ...