13.12.5
Settings
GUID-F573CA16-4821-4203-970A-F7D01AF5E63B v1
This function does not have any setting parameters.
13.12.6
Operation principle
SEMOD176587-4 v6
An example is used to explain the principle of operation: With integer 15 sent to
and received by the ITBGAPC function on the IEC 61850 the OUTx changes from
0 to 1 on each of the OUT1; OUT2 OUT3 and OUT4. All other OUTx (5≤x≤16)
remains 0. The boolean interpretation of this is represented by the assigned values
of each of the outputs OUT1 = 1; and OUT2 = 2; and OUT3= 4; and OUT4 = 8.
The sum of these OUTx (1≤x≤4) is equal to the integer 15 received via the IEC
61850 network. The remaining OUTx = 0 for (5≤x≤16).
OUTx represents a value when activated. The value of each of the OUTx is in
accordance with the Table
. When not activated the OUTx has the value 0.
The value of each OUTx for 1≤x≤16 (1≤x≤16) follows the general formulae:
OUTx = 2
x-1
The sum of the values of all activated OUTx = 2
x-1
where 1≤x≤16
will be equal to the integer value received over IEC 61850 to the ITBGAPC_1
function block.
The Integer to Boolean 16 conversion with logic node representation function
(ITBGAPC) will transfer an integer with a value between 0 to 65535
communicated via IEC 61850 and connected to the ITBGAPC function block to a
combination of activated outputs OUTx where 1≤x≤16. The values represented by
the different OUTx are according to Table
. When an OUTx is not activated, its
value is 0.
The ITBGAPC function is designed for receiving the integer input from a station
computer - for example, over IEC 61850. If the BLOCK input is activated, it will
freeze the logical outputs at the last value.
Table 350:
Outputs and their values when activated
Name of OUTx
Type
Description
Value when
activated
Value when
deactivated
OUT1
BOOLEAN
Output 1
1
0
OUT2
BOOLEAN
Output 2
2
0
OUT3
BOOLEAN
Output 3
4
0
OUT4
BOOLEAN
Output 4
8
0
OUT5
BOOLEAN
Output 5
16
0
OUT6
BOOLEAN
Output 6
32
0
OUT7
BOOLEAN
Output 7
64
0
OUT8
BOOLEAN
Output 8
128
0
OUT9
BOOLEAN
Output 9
256
0
OUT10
BOOLEAN
Output 10
512
0
Table continues on next page
Section 13
1MRK 506 382-UEN A
Logic
516
Line distance protection REL650 2.2 IEC
Technical manual
Содержание RELION 650 SERIES
Страница 1: ...RELION 650 SERIES Line distance protection REL650 Version 2 2 Technical manual ...
Страница 2: ......
Страница 46: ...40 ...
Страница 56: ...50 ...
Страница 164: ...158 ...
Страница 264: ...258 ...
Страница 304: ...298 ...
Страница 320: ...314 ...
Страница 338: ...332 ...
Страница 438: ...432 ...
Страница 468: ...462 ...
Страница 534: ...528 ...
Страница 646: ...640 ...
Страница 660: ...654 ...
Страница 676: ...670 ...
Страница 800: ...794 ...
Страница 836: ...830 ...
Страница 890: ...884 ...
Страница 894: ...888 ...
Страница 940: ...934 ...
Страница 941: ...935 ...