Directional mode can be set to
Off
/
Non-directional
/
Forward
/
Reverse
. By this
parameter setting the directional mode of the step is selected.
•
Residual current start value.
•
Type of operating characteristic (inverse or definite time). By this parameter
setting it is possible to select inverse or definite time delay for the earth-fault
protection. Most of the standard IEC and ANSI inverse characteristics are
available. For the complete list of available inverse curves, please refer to
section
.
•
Type of reset characteristic (
Instantaneous
/
IEC Reset
/
ANSI Reset
). By this
parameter setting it is possible to select the reset characteristic of the step. For
the complete list of available reset curves, please refer to section
•
Time delay related settings. By these parameter settings the properties like
definite time delay, minimum operating time for inverse curves, reset time
delay and parameters to define user programmable inverse curve are defined.
•
Supervision by second harmonic blocking feature (
On
/
Off
). By this parameter
setting it is possible to prevent operation of the step if the second harmonic
content in the residual current exceeds the preset level.
•
Multiplier for scaling of the set residual current pickup value by external
binary signal. By this parameter setting it is possible to increase residual
current pickup value when function binary input ENMULTx has logical value
1.
•
The operation current value
INx>
, is limited to be between
INx>Max
and
INx>Min
. The default values of the limits are the same as the setting limits for
INx>, and the limits can only be used for reducing the allowed range of INx>.
This feature is used when remote setting of the operation current value is
allowed, making it possible to ensure that the operation value used is
reasonable. If INx> is set outside INx>Max and INx>Min, the closest of the
limits to INx> is used by the function. If
INx>Max
is smaller then
INx>Min
,
the limits are swapped. The principle of the limitation is shown in Figure
.
hi
u
lo
y
MIN
MAX
INx>_used
INx>Max
INx>
INx>Min
IEC17000017-1-en.vsdx
IEC17000017 V1 EN-US
Figure 91:
Logic for limitation of used operation current value
Simplified logic diagram for one residual overcurrent step is shown in Figure
Section 7
1MRK 506 382-UEN A
Current protection
196
Line distance protection REL650 2.2 IEC
Technical manual
Содержание RELION 650 SERIES
Страница 1: ...RELION 650 SERIES Line distance protection REL650 Version 2 2 Technical manual ...
Страница 2: ......
Страница 46: ...40 ...
Страница 56: ...50 ...
Страница 164: ...158 ...
Страница 264: ...258 ...
Страница 304: ...298 ...
Страница 320: ...314 ...
Страница 338: ...332 ...
Страница 438: ...432 ...
Страница 468: ...462 ...
Страница 534: ...528 ...
Страница 646: ...640 ...
Страница 660: ...654 ...
Страница 676: ...670 ...
Страница 800: ...794 ...
Страница 836: ...830 ...
Страница 890: ...884 ...
Страница 894: ...888 ...
Страница 940: ...934 ...
Страница 941: ...935 ...