This mode is used for all LEDs that are used to indicate a disturbance. The LEDs will
stay in the last state after the disturbance run time until they are reset after a
defined time.
•
The timers are set in Parameter Setting tool in the function block LEDGEN.
IEC09000657-1-en.vsd
IEC09000657 V1 EN-US
Figure 45: LHMI: LED operation mode
6.1.2
LED operation modes
GUID-40B89A33-3C2D-488C-8932-F862E0C9F477 v3
Description of different operation modes for LEDs to be configured in Application
Configuration tool and Parameter Setting tool.
Six operation modes are listed in the drop down menu in Parameter Setting tool.
•
Follow-S
•
Follow-F
•
LatchedAck-F-S
•
LatchedAck-S-F
•
LatchedColl-S
•
LatchedReset-S
LED operation mode Follow-S
IEC08000395.vsd
= Steady
= Flash
Illumination =>
R
Y
G
R
Y
G
S
ig
na
ls
LE
D
IEC08000395 V1 EN-US
Figure 46: LHMI: LED operation mode Follow-S
Monitoring a signal with a LED is a simple mode, where the LED follows the signal state. More
than one signal per LED can be used when applicable. See
The LED illuminates always in steady state.
1MRK 511 284-UEN B
Section 6
Local HMI engineering
650 series
57
Engineering manual
© Copyright 2013 ABB. All rights reserved