Values of the logical signals for GUPPDUP (37) are available on the local HMI under
Main menu/Tests/Function status/Current/GUPPDUP(37,P<)/1:GUPPDUP
. The
Signal Monitoring in PCM600 shows the same signals that are available on the local HMI.
6.4.14.1
Verifying the settings
The underpower protection shall be set to values according to the real set values to be
used.
The test is made by means of injection of voltage and current where the amplitude of
both current and voltage and the phase angle between the voltage and current can be
controlled. During the test, the analog outputs of active and reactive power shall be
monitored.
1.
Connect the test set for injection of voltage and current corresponding to the
mode to be used in the application. If a three-phase test set is available this could
be used for all the modes. If a single-phase current/voltage test set is available the
test set should be connected to a selected input for one-phase current and voltage.
Use the formulas stated in
for the different calculation modes used. The
set mode
Mode
can be found on the local HMI under
Main menu/Settings/IED
Settings/Current/GUPPDUP(37,P<)/1:GUPPDUP/General
.
Table 9:
Calculation modes
Set value:
Mode
Formula used for complex power calculation
A, B, C
*
*
*
A
A
B
B
C
C
S V
I
V
I
V
I
=
×
+
×
+
×
EQUATION2055 V1 EN
(Equation 4)
Arone
*
*
AB
A
BC
C
S V
I
V
I
=
×
-
×
EQUATION2056-ANSI V1 EN
(Equation 5)
PosSeq
*
3
PosSeq
PosSeq
S
V
I
= ×
×
EQUATION2057-ANSI V1 EN
(Equation 6)
AB
*
*
(
)
AB
A
B
S V
I
I
=
×
-
EQUATION2058-ANSI V1 EN
(Equation 7)
Table continues on next page
Section 6
1MRK 506 331-UUS A
Testing functionality
88
Commissioning Manual