IEC09000630-1-en.vsd
IEC09000630 V1 EN
Figure 68:
CCT600 data sets default content
3.2. Configure and/or re-configure the default data sets.
Note that reporting data sets shall only contain data intended
to be used by clients, for example for event handling.
The data set for GOOSE may contain signals on data
attribute level or on FCDA level. The latter is also called
structured GOOSE
.
3.3. Configure additional Report Control Blocks when needed for each data set
used for vertical communication.
1MRK 511 245-UUS -
Section 7
IEC 61850 communication engineering
650 series ANSI
101
Engineering Manual