2  Quick start guide

 | Relion

®

 630 series

Accessing main menu

Press 

 to navigate between main menu and default screen.

Controlling circuit breakers and disconnectors

The primary equipment can be controlled via the LHMI with 
the Open and Close buttons when the IED is set to local 
control mode and the user is authorized to access control 
operations. Select 

Main menu 

 Control

 and the SLD 

will display all controllable objects. Select the object with 

 

or 

. Currently selected object is indicated with a square 

border. Press 

 to open or 

 to close the object.

Changing the display contrast

Hold 

 and press 

 or 

 to change the display contrast. 

To store a selected contrast, change the ContrastLevel 
parameter via 

Main menu 

 Configuration 

→ 

HMI 

→ 

LHMI.

Changing the language

Main menu 

 Language 

and press 

. Change the 

language using 

 or 

. Press 

 to confirm the selection. 

Commit the changes. All languages that are available in 
the firmware version loaded are visible. Most of the IED‘s 
parameters can be changed in the same way as language.

Changing the default view

The default view of the display is Main menu unless set 
otherwise.

Select 

Main menu 

 Configuration 

 HMI 

 LHMI 

 DefaultScreen 

and press 

 to confirm the selection.

Change the default view with 

 or 

 and press 

 to 

confirm the selection.

Clearing events and indications

Go to clear menu by pressing 

 or selecting Clear from the 

main menu. Then select what you want to clear with 

 and 

 keys. Press 

, select OK to confirm the selection or 

Cancel to cancel the selection and press 

.

Changing the overcurrent start value

The IED contains only one setting group by default. The 
number of setting groups can be selected from 1 to 4.

Main menu 

 Settings 

 Settings 

 

select 

setting group, 1 and press 

 

→ 

Current Protection 

 PHLPTOC1(51P-1;3I>):1 

 Start value

.

Press 

 and change the value by using 

 or 

 or 

 

or 

 keys. Press 

 when the setting value is correct. You 

can change all settings in the same way. The most common 
function block names are described at the end of this 
document.

Saving settings

After making changes to parameters they have to be saved 
to get them into use. Save the settings by going back to main 
menu by pressing 

 or using the 

 key. When IED asks 

confirmation to save setting, answer “Yes“. Settings will be 
effective as soon as you accept the “yes“ except from some 
parameters marked with a ! require the IED to be rebooted 
before the changes can be taken into use.

Monitoring alarm data

Active alarms are indicated by the alarm LEDs and the LED 
in the Multipage button. The alarms are configured with 
PCM600. The alarm type and information depend on the 
application configuration. Press 

 to open the alarm view. 

Press 

 or 

 to move between the active alarms in the 

current page, or press 

 to switch between the three alarm 

pages. Press 

 to open a dialog box that shows more 

detailed information about the selected alarm.

Checking the value of currents and voltages of the last 
fault

Main menu 

 Disturbance records 

 Select the 

Record 

 Trip values

Checking IED order code, serial number, production date 
and product version

Main menu 

 Information 

 Product Identifiers

Checking IED status

The IED self-supervision handles internal run-time fault 
situations. The main indication of an internal fault is a flashing 
green Ready LED. More detailed information can be found 
from  

Menu 

 Monitoring 

 IED Status

Rebooting the IED

Reboot the IED by switching the auxiliary power off and then 
back on.

Using the function buttons

The function buttons can be configured either as menu 
shortcuts or control buttons. Configurations can be made with 
PCM600. The buttons are functional only when the function 
button panel is visible.

Press any function button to open the function button panel, 
no other actions will happen on the first press. After the panel 
is open press the wanted button to either jump to a certain 
menu item or hold it for at least half a second to initiate a 
control signal. Press 

 to close the function button panel.

Using the local HMI

Complete customer documentation is available in the product 
pages that can be accessed through 

www.abb.com/relion.