Characteristic
Value
Reset time
40 ms
Trip time accuracy
±1.0% of the set value of ±20 ms
Suppression of harmonics
-50 dB at f = n × f
n
, where n = 2, 3, 4, 5,…
1) VG = 1.0 × Vn
2) Includes the delay of the signal output contact, results based on statistical distribution of 1000
measurements
4.2.4.11
Technical revision history
Table 387:
21YN Technical revision history
Technical revision
Change
B
Internal improvement.
C
Voltage pickup value setting range and default value
change.
D
Internal improvement.
E
Internal improvement.
4.2.5
Harmonics-based ground-fault protection 51NHA
4.2.5.1
Identification
Description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Harmonics-based ground-fault
protection
HAEFPTOC
Io>HA
51NHA
4.2.5.2
Function block
51NHA
I_REF_RES
BLOCK
PICKUP
TRIP
IG
GUID-9A831169-A6A0-4689-9715-A61794979C12 V1 EN
Figure 192:
Function block
4.2.5.3
Functionality
The harmonics-based ground-fault protection function 51NHA is used instead of a
traditional ground-fault protection in networks where a fundamental frequency
component of the bround-fault current is low due to compensation.
1MAC059074-MB A
Section 4
Protection functions
615 series ANSI
401
Technical Manual
Содержание Relion 615 series
Страница 1: ... RELION PROTECTION AND CONTROL 615 series ANSI Technical Manual ...
Страница 2: ......
Страница 39: ...Section 17 Glossary 1181 Table of contents 615 series ANSI 33 Technical Manual ...
Страница 40: ...34 ...
Страница 64: ...58 ...
Страница 210: ...3 19 4 Settings Section 3 1MAC059074 MB A Basic functions 204 615 series ANSI Technical Manual ...
Страница 216: ...210 ...
Страница 884: ...878 ...
Страница 1038: ...1032 ...
Страница 1136: ...1130 ...
Страница 1172: ...1166 ...
Страница 1180: ...1174 ...
Страница 1186: ...1180 ...
Страница 1192: ...1186 ...
Страница 1193: ...1187 ...
Страница 1194: ......
Страница 1195: ......