Fault indication
Fault code
Additional information
Internal Fault
Conf. error,X130
66
Card in slot X130 is wrong type, is
missing or does not belong to the original
composition.
Internal Fault
Card error,X000
72
Card in slot X000 is faulty.
Internal Fault
Card error,X100
73
Card in slot X100 is faulty.
Internal Fault
Card error,X110
74
Card in slot X110 is faulty.
Internal Fault
Card error,X120
75
Card in slot X120 is faulty.
Internal Fault
Card error,X130
76
Card in slot X130 is faulty.
Internal Fault
LHMI module
79
LHMI module is faulty. The fault
indication may not be seen on the LHMI
during the fault.
Internal Fault
RAM error
80
Error in the RAM memory on the CPU
card.
Internal Fault
ROM error
81
Error in the ROM memory on the CPU
card.
Internal Fault
EEPROM error
82
Error in the EEPROM memory on the
CPU card.
Internal Fault
FPGA error
83
Error in the FPGA on the CPU card.
Internal Fault
RTC error
84
Error in the RTC on the CPU card.
Internal Fault
RTD card error,X130
96
RTD card located in slot X130 may have
permanent fault. Temporary error has
occurred too many times within a short
time.
7.2.2
Warnings
Warnings are indicated with the text
Warning
additionally provided with the
name of the warning, a numeric code, and the date and time on the LHMI. The
warning indication message can be manually cleared.
If a warning appears, record the name and code so that it can be provided to ABB
customer service.
Section 7
1MRS756708 C
Troubleshooting
90
615 series