Table 11:

Disturbance channel identification

ACC Number Signal

1

Phase current IL1-A

2

Phase current IL2-A

3

Phase current IL3-A

4

Neutral current Io-A

5

Phase voltage U1-A or phase-to-phase voltage U12-A

6

Phase voltage U2-A or phase-to-phase voltage U23-A

7

Phase voltage U3-A or phase-to-phase voltage U31-A

8

Neutral voltage Uo-A

Private channel numbers

64

Neutral current Io-B

65

Phase current IL1-B

66

Phase current IL2-B

67

Phase current IL3-B

68

Neutral voltage Uo-B

69

Phase voltage U1-B or phase-to-phase voltage U12-B

70

Phase voltage U2-B or phase-to-phase voltage U23-B

71

Phase voltage U3-B or phase-to-phase voltage U31-B

Disturbance recorder channels are the physical measurement inputs to the IED. It
depends on the IED type if all the disturbance recorder channel signals are available
or not. The IED may measure voltages either between phase and ground or between
phases. The contents in ACC 5...8 and 69...71 are coupled directly to these voltage
measurements.

The default setting of the native disturbance recorder supports the
channels, meaning physical analog input channels, listed in 

Table 11

.

User-defined channels in the 60870-5-103 files appear as ACC=255
(unknown channel).

Disturbance recorder channels can be selected from the disturbance
recorder configuration settings. Only the selected channels are
included in the 60870-5-103 files.

3.5.3 

Disturbance recorder tags identification

According to the IEC 60870-5-103 standard the disturbance recorder tags (digital
signals) are identified by the same function type/information number combination
that corresponds to the signal in the normal IEC 60870-5-103 Class 1 event transfer.

Section 3

1MRS759001 A

Vendor-specific implementation

28

615 series

Communication Protocol Manual

Содержание Relion 615 series

Страница 1: ...RELION PROTECTION AND CONTROL 615 series IEC 60870 5 103 Communication Protocol Manual...

Страница 2: ......

Страница 3: ...Document ID 1MRS759001 Issued 2019 04 30 Revision A Product version 5 0 FP1 Copyright 2019 ABB All rights reserved...

Страница 4: ...bed in this document is furnished under a license and may be used copied or disclosed only in accordance with the terms of such license Trademarks ABB and Relion are registered trademarks of the ABB G...

Страница 5: ...ted and communicate data and information via a network interface which should be connected to a secure network It is the sole responsibility of the person or entity responsible for network administrat...

Страница 6: ...al equipment for use within specified voltage limits Low voltage directive 2014 35 EU This conformity is the result of tests conducted by the third party testing laboratory Intertek in accordance with...

Страница 7: ...ic counters 11 IEC 60870 5 103 process data 12 IEC 60870 5 103 data objects 12 Indications 12 ASDU 2 type fault number and relative time data 13 Configuring of IEC 60870 5 103 indications 13 Class 1 e...

Страница 8: ...ction type 25 Device identification code 25 Time synchronization 26 Block monitoring 26 Disturbance recorder file transfer 26 Disturbance recorder file directory ASDU 23 26 Disturbance recorder channe...

Страница 9: ...s the communication system engineer or system integrator responsible for pre engineering and engineering the communication setup in a substation from a protection relay s perspective The system engine...

Страница 10: ...61850 engineering guide Point list manual Cyber security deployment guideline GUID 12DC16B2 2DC1 48DF 8734 0C8B7116124C V2 EN Figure 1 The intended use of documents during the product life cycle Prod...

Страница 11: ...nder certain operational conditions operation of damaged equipment may result in degraded process performance leading to personal injury or death Therefore comply fully with all warning and caution no...

Страница 12: ...ssages and monitored data names are shown in Courier font When the function starts the START output is set to TRUE This document assumes that the parameter setting visibility is Advanced Section 1 1MR...

Страница 13: ...pplication data 5 4 Definition and coding of application information elements 5 5 Basic application functions 5 6 Conformance testing guidelines 5 103 Companion standard for the informative interface...

Страница 14: ...roblems with older installations every available IEC 60870 5 103 process data point can be freely remapped with PCM600 All the mapped data is not in use by default 2 2 Documentation Address informatio...

Страница 15: ...overflows should be treated and reported ASDU type 2 data is generally supported This means the generation of a fault number and a relative time stamp for protection related Class 1 events Despite the...

Страница 16: ...o protocol instances is in use I3CLPRT EC_FRZ STATUS GUID B230DC02 9257 4A70 A16D 2FC4A9D35CD6 V1 EN Figure 2 Function block By default Instance 1 is active in the IED but needs to be set On by the Op...

Страница 17: ...frames and link errors The serial drivers COMn have their own diagnostic counters for lower level serial communication character error and link messages The COMn counters count all the messages on th...

Страница 18: ...ntical For a list of the available data objects see the point list manual 3 3 2 Indications The IEC 60870 5 103 standard defines indications to be of ON OFF type The value coding for indications is al...

Страница 19: ...tions Change GI assignment of indications Change ASDU type used by the indications Change the data coding value DPI representation four pole objects only Suppress falling edge Class 1 events non stand...

Страница 20: ...erflow operation in the IED The setting parameters are located in Configuration Communication IEC 60870 5 103 I3C0n parameter suffix n 1 or 2 depending on the instance Class1OvInd n takes the overflow...

Страница 21: ...0870 5 103 Class 1 data In older IED versions the LED object had only two positions Off and Alarm red The corresponding IEC 60870 5 103 Class1 LED data area shows DPI values off 01 for Off and values...

Страница 22: ...red maximum current and voltage values during a fault and fault locator registrations For example also tap changer position values can be obtained through TypeID 4 There is no internal prioritization...

Страница 23: ...be controlled ON If the IED is in local mode the remote CB controls are rejected 3 3 4 1 Circuit breaker control model Circuit breaker can only be controlled with DIRECT ON OFF commands This is due to...

Страница 24: ...and is rejected on link level Link NAK DFC 1 Remote command performed on a non existing object The command is rejected on link level Link NAK DFC 0 In the last two cases the DFC flag is used to distin...

Страница 25: ...the corresponding values are set as constant 0 Trailing 0 values are cut from the frame and the frame becomes shorter The default function type information number definitions for frame 6 are FUN 10 IN...

Страница 26: ...IEC 60870 5 103 measurand Values 1 2 and 2 4 are standard values but the IED can actually accept any value For example scale 4 0 for IL1 enlarges the measurand range to 4 0 In 4 0 In The IEC 60870 5...

Страница 27: ...to collect registrations belonging to the same fault situation ASDU 4 events can easily fill up the Class 1 event buffer The fault record can for example be configured to register only after an operat...

Страница 28: ...esent IED real time Thereafter ASDU205 counter events are created into Class1 buffer Some alternatives for EC_FRZ activation A common alternative for the operation is that counters should be frozen an...

Страница 29: ...ll over value The roll over values can be defined through the Communication Management tool Scale value Default setting is 1000000000 999999999 1 3 3 7 Accessing of non protocol mapped data The protec...

Страница 30: ...y protocol as regular protocol application data General purpose input object and OR function block may cause delays to time stamps 3 4 Other IEC 60870 5 103 data 3 4 1 Changing of parameter setting gr...

Страница 31: ...all IEC 60870 5 103 data points that have their function type defined as 0 The user has to assure that no similar IEC 60870 5 103 point definitions already exist with the same function type and inform...

Страница 32: ...ts into IEC 60870 5 103 disturbance data Disturbance files are also available as standard COMTRADE files through PCM600 or WHMI IEC 60870 5 103 disturbance recorder spontaneous Class 1 notification me...

Страница 33: ...stem Disturbance recorder files can be deleted by the IEC 60870 5 103 master The recorder file is deleted by the IED after it has been sent to the IEC 60870 5 103 master according to the standard Dist...

Страница 34: ...channel signals are available or not The IED may measure voltages either between phase and ground or between phases The contents in ACC 5 8 and 69 71 are coupled directly to these voltage measurement...

Страница 35: ...nless the IEC 60870 5 103 master does not abort the transmission Disturbance recorder transfer verification The IEC 60870 5 103 disturbance recorder file transfer implemented in the IED has been verif...

Страница 36: ...cycle operates as defined by the standard GI optimization strives to send less data to the master through the Class 1 report The GI optimization in the IED is based on two facts It is enough to send a...

Страница 37: ...at has been done in advance This configuration can be modified with PCM600 It is also possible to start a completely new configuration from an emptied configuration state in Application Configuration...

Страница 38: ...32...

Страница 39: ...led Serial port 1 COM 1 2 COM 2 1 COM 1 COM port Address 1 255 1 1 Unit address Mapping select 1 2 1 1 Mapping selection Start delay 0 20 char 1 4 Start frame delay in chars End delay 0 20 char 1 4 En...

Страница 40: ...use 0 User frame 1 Standard frame 1 2 Standard frame 2 3 Standard frame 3 4 Standard frame 4 5 Standard frame 5 6 Private frame 6 7 Private frame 7 1 Not in use Active Class2 Frame 3 Frame4InUse 1 No...

Страница 41: ...f Monitoring Direction Internal Overflow 0 False 1 True 0 False Internal Overflow TRUE System level overflow occured indication only EC_FRZ 0 False 1 True 0 False Control point for freezing energy cou...

Страница 42: ...36...

Страница 43: ...flow control DPI Double point information EIA 485 Serial communication standard according to Electronics Industries Association EMC Electromagnetic compatibility FAN Fault number FUN Function type GI...

Страница 44: ...ger Reset CU Reset communication unit Reset FCB Reset flow control bit SOF Status of fault SW Software TEST Disturbance data recorded in test mode bit TM Disturbance data transmission in progress bit...

Страница 45: ...39...

Страница 46: ......

Страница 47: ......

Страница 48: ...C Power Grid Automation Co Ltd No 39 Shuige Road Jiangning District 211153 Nanjing China Phone 86 25 69832000 Fax 86 25 69833000 www abb com substationautomation Copyright 2019 ABB All rights reserved...

Отзывы: