Table 45. Arc protection (ARCSARC)
Characteristic
Value
Operation accuracy
±3% of the set value or ±0.01 × I
n
Operate time
Minimum
Typical
Maximum
Operation mode = "Light only"
9 ms
4 ms
10 ms
6 ms
12 ms
7 ms
Reset time
Typically 40 ms
Reset ratio
Typically 0.96
Table 46. Arc protection (ARCSARC) main settings
Parameter
Function
Value (Range)
Step
Phase start value
ARCSARC
0.50...40.00 × I
n
0.01
Ground start value
ARCSARC
0.05...8.00 × I
n
0.01
Operation mode
ARCSARC
2 = Light only
3 = BI controlled
-
Table 47. Multipurpose protection (MAPGAPC)
Characteristic
Value
Operation accuracy
±1.0% of the set value or ±20 ms
Table 48. Multipurpose protection (MAPGAPC) main settings
Parameter
Function
Value (Range)
Step
Start value
MAPGAPC
-10000.0...10000.0
0.1
Operate delay time
MAPGAPC
0...200000 ms
100
Operation mode
MAPGAPC
1 = Over
2 = Under
-
Table 49. Load-shedding and restoration (LSHDPFRQ)
Characteristic
Value
Operation accuracy
f<
±5 mHz
df/dt
±100 mHz/s (in range |df/dt| < 5 Hz/s)
± 2.0% of the set value (in range 5 Hz/s < |df/dt| < 15 Hz/s)
Start time
f<
<80 ms
df/dt
<120 ms
Reset time
<150 ms
Operate time accuracy
±1.0% of the set value or ±30 ms
Voltage Protection and Control
1MRS757058 K
REU615
Product version: 5.0 FP1
ABB
33