IECA070698 V1 EN
Figure 113:
Three-phase current quantities during the broken conductor fault in
phase A with the ratio of negative-sequence and positive-sequence
currents
4.4.2.6
Signals
Table 242:
PDNSPTOC Input signals
Name
Type
Default
Description
I
1
SIGNAL
0
Positive sequence current
I
2
SIGNAL
0
Negative sequence current
I_A
SIGNAL
0
Phase A current
I_B
SIGNAL
0
Phase B current
I_C
SIGNAL
0
Phase C current
BLOCK
BOOLEAN
0=False
Block signal for activating the blocking mode
Table 243:
PDNSPTOC Output signals
Name
Type
Description
OPERATE
BOOLEAN
Operate
START
BOOLEAN
Start
4.4.2.7
Settings
Table 244:
PDNSPTOC Group settings (Basic)
Parameter
Values (Range)
Unit
Step
Default
Description
Start value
10...100
%
1
10
Start value
Operate delay time
100...30000
ms
1
100
Operate delay time
1MRS757454 D
Section 4
Protection functions
611 series
237
Technical Manual