Table 229:
HIBPDIF Monitored data
Name
Type
Values (Range)
Unit
Description
START_DUR
FLOAT32
0.00...100.00
%
Ratio of start time /
operate time
HIBPDIF
Enum
1=on
2=blocked
3=test
4=test/blocked
5=off
Status
Table 230:
HICPDIF Monitored data
Name
Type
Values (Range)
Unit
Description
START_DUR
FLOAT32
0.00...100.00
%
Ratio of start time /
operate time
HICPDIF
Enum
1=on
2=blocked
3=test
4=test/blocked
5=off
Status
4.3.1.10
Technical data
Table 231:
HIxPDIF Technical data
Characteristic
Value
Operation accuracy
Depending on the frequency of the current
measured: f
n
±2 Hz
±1.5% of the set value or ±0.002 × I
n
Start time
1)2)
Minimum
Typical
Maximum
I
Fault
= 2.0 × set
Start
value
12 ms
16 ms
24 ms
I
Fault
= 10 × set
Start
value
10 ms
12 ms
14 ms
Reset time
<40 ms
Reset ratio
Typically 0.96
Retardation time
<35 ms
Operate time accuracy in definite time mode
±1.0% of the set value or ±20 ms
1)
Measurement mode = default (depends on stage), current before fault = 0.0 × I
n
, f
n
= 50 Hz, fault current
with nominal frequency injected from random phase angle, results based on statistical distribution of
1000 measurements
2) Includes the delay of the signal output contact
4.3.1.11
Technical revision history
Table 232:
HIxPDIF Technical revision history
Technical revision
Change
B
Function name changed from HIPDIF to HIAPDIF,
HIBPDIF, HICPDIF
1MRS757454 D
Section 4
Protection functions
611 series
227
Technical Manual
Содержание Relion 611 Series
Страница 1: ... RELION PROTECTION AND CONTROL 611 series Technical Manual ...
Страница 2: ......
Страница 22: ...16 ...
Страница 30: ...24 ...
Страница 308: ...302 ...
Страница 400: ...394 ...
Страница 506: ...500 ...
Страница 516: ...510 ...
Страница 522: ...516 ...
Страница 528: ...522 ...
Страница 533: ...527 ...
Страница 534: ......
Страница 535: ......