8

T8 breaker trip unit - RELT set up 
instructions

RELT function is factory enabled.
Threshold value cab to be adjusted per a performed 
coordination study as applicable

T8 PR332/P Trip Unit Default PIN # is: 0001    

Press ESC

Select «Protection»
Press Enter

Scroll down to «ON»
Press Enter arrow pushbutton

Scroll down to «Threshold MM»
Press Enter arrow pushbutton

Adjust the threshold using UP and Down Arrows pushbuttons
Press Enter arrow pushbutton to leave the page
Than press ESC pushbutton

Press Press Enter arrow pushbutton to «confirm» the settings

Scroll down to «MM Protection» 
Press Enter arrow pushbutton

Select «Enable»
Press Enter arrow pushbutton

Содержание ReliaMod RMM B 4R

Страница 1: ...ones en espa ol v ase la p gina 16 HAZARDOUS VOLTAGE WILL CAUSE SEVERE INJURY OR DEATH Turn OFF power supplying this equipment before working inside Please read these instructions completely before in...

Страница 2: ...Mounting of units Meter module Electrical code or project spec Electrical code or project spec Grade level Utility spec Min meter position Utility spec Max meter position Main module V2 V1 X2 X1 A Y Z...

Страница 3: ...52 5 8 RMM_BB20R 60 5 8 38 5 16 24 3 16 8 52 5 8 Main Lug Module RMM_L4R 48 13 3 4 6 1 2 15 15 16 32 1 16 RMM_L6R 47 15 16 16 3 4 6 1 2 14 5 16 33 5 8 RMM_L8R 47 15 16 20 5 16 11 1 4 12 7 8 35 1 16 RM...

Страница 4: ...7 8 18 3 8 9 5 8 35 5 16 48 9 16 27 7 16 20 9 16 Commercial Lever Bypass LVBP 225A and 400 Socket RMS_12122CHLBR 54 1 16 19 5 8 9 11 16 24 1 2 29 9 16 n a 4 11 16 RMS_12222CHLBR 54 1 16 19 5 8 9 11 16...

Страница 5: ...ttom end walls on main modules can be removed from the enclosure to ease the punching of holes for bot tom fed conduit and conductors the mounting screws to maintain NEMA 3R enclosure rating The embos...

Страница 6: ...need to bond the neutral use the bonding jumper supplied with the unit Unfasten from the factory installed position Rotate jumper and fasten to the neutral bus at torque indicated on label in unit Se...

Страница 7: ...Trip Unit Default PIN is 00001 The following is a step by step guide for implementing RELT settings and ensuring proper operation of the RELT function for XT7 touch trip units Enter the submenu for th...

Страница 8: ...ct Protection Press Enter Scroll down to ON Press Enter arrow pushbutton Scroll down to Threshold MM Press Enter arrow pushbutton Adjust the threshold using UP and Down Arrows pushbuttons Press Enter...

Страница 9: ...f Complete the fastening of the breaker to its mounting plate by torquing the mounting screws to 10 in lbf THQL THHQL are plug in type breakers All other breakers are bolt on Installation of A1 breake...

Страница 10: ...ker Installation of XT3 Breakers Mount breaker on its plate with the straps aligned with busbars on the meter module Use the mounting screws included in the breaker package to fasten the breaker to th...

Страница 11: ...s 1 Gang 2 Gang 3 Gang 4 Gang 5 Gang 6 Gang 1 meter at the top A C A C A C A C A C A C 2 A B A B A B A B A B 3 B C B C B C B C 4 A C A C A C A C 5 A B A B 6 B C Position A C Position A B Position B C...

Страница 12: ...ion B C to position A B 4 Install strap in position C 5 Tighten all connections to 170 in lbf Conversion from A C to A B 2 Remove meter barrier at location to convert 3 Remove C phase strap 4 Install...

Страница 13: ...and insulation sheet 6 Tighten all connections to 170 in lbf 7 Re install meter barrier Conversion from B C to A B 2 Remove meter barrier at location to convert 3 Remove C phase strap 4 Switch phase...

Страница 14: ...meter jaws and disactivate the bypass 6 Replace the ringless meter cover NOTE Meter cover cannot be installed with the lever in the bypass mode Warning Hazardous Voltage can cause serious injury or d...

Страница 15: ...h the meter module Remove inch knockout and install sealing screw provided Install utility seal through the hole in the sealing screw and the slot in the hasp Provision for utility seal Provision for...

Страница 16: ...de este equipo antes de realizar cualquier trabajo dentro o fuera de l Lea atentamente estas instrucciones antes de instalar o retirar el dispositivo Una instalaci n incorrecta podr a resultar peligro...

Страница 17: ...o o especificaci n del proyecto C digo el ctrico o especificaci n del proyecto Nivel de grado Requisito de la empresa de servicio publico Posici n min del medidor Requisito de la empresa de servicio p...

Страница 18: ...5 8 38 5 16 24 3 16 8 52 5 8 Modulo principal con zapatas RMM_L4R 48 13 3 4 6 1 2 15 15 16 32 1 16 RMM_L6R 47 15 16 16 3 4 6 1 2 14 5 16 33 5 8 RMM_L8R 47 15 16 20 5 16 11 1 4 12 7 8 35 1 16 RMM_L12R...

Страница 19: ...comercial LVBP de 225A y toma de 400A RMS_12122CHLBR 54 1 16 19 5 8 9 11 16 24 1 2 29 9 16 n a 4 11 16 RMS_12222CHLBR 54 1 16 19 5 8 9 11 16 24 1 2 29 9 16 9 5 16 4 11 16 RMS_12322CHLBR 68 1 16 19 5 8...

Страница 20: ...venden por separado Conductores de L nea alimentados por el fondo Las paredes inferiores de los m dulos principales pueden retirarse de la caja para facilitar la perforaci n de orificios para conducto...

Страница 21: ...nidad Desabrochar desde la posici n de instalaci n en f brica Gire el puente y f jelo al bus neutro al par indicado en la etiqueta de la unidad Fije el puente a la caja con la torniller a suministrada...

Страница 22: ...PIN predeterminado es 00001 La siguiente es una gu a paso a paso para implementar los ajustes RELT y garantizar el correcto funcionamiento de la funci n RELT para las unidades de disparo por contacto...

Страница 23: ...eleccione Protecci n Pulse Intro Despl cese hasta ON Pulse el bot n de flecha Intro Despl cese hasta Umbral MM Pulse el bot n de flecha Intro Ajuste el umbral con los pulsadores de flecha ARRIBA y ABA...

Страница 24: ...la fijaci n del interruptor a su placa de montaje apretando los tornillos de montaje a 10 in lbf THQL THHQL son interruptores autom ticos enchufables Todos los dem s disyuntores son atornillables Ins...

Страница 25: ...vez instalados los conductores Formula A2 marco disyuntores XT4 marco disyuntores XT3 marco disyuntores Instalaci n de disyuntores XT3 Monte el disyuntor en su placa con las correas alineadas con las...

Страница 26: ...iento Phase Link 3 8 Herrajes 1 Desconecte la alimentaci n del equipo Conversi n de A C a B C 2 Retire la correa en la posici n A 3 Instale el enlace de fase el aislamiento y el perno 3 8 en la posici...

Страница 27: ...as las conexiones a 170 in lbf Conversi n de A C a A B 2 Quitar la barrera del contador en el lugar a convertir 3 Quitar la correa de la fase C 4 Instale el enlace de fase el aislamiento y el perno 3...

Страница 28: ...te todas las conexiones a 170 in lbf 7 Volver a instalar la barrera de contadores Conversi n de B C a A B 2 Quitar la barrera del contador en el lugar a convertir 3 Quitar la correa de la fase C 4 Int...

Страница 29: ...mand bula a la derecha Funci n de derivaci n de la palanca Instalaci n o sustituci n delcontador en un m dulo contador de derivaci n de palanca PRECAUCI N Debe ser realizado por personal de servicio a...

Страница 30: ...lado suministrado con el m dulo contador Retire el orificio ciego de de pulgada e instale el tornillo de sellado suministrado Instale la junta de estanqueidad a trav s del orificio del tornillo de est...

Отзывы: