26
R E LI AG E A R
®
N D A NS I N A R ROW DE S IG N ME TA L- CL A D S WITCHG E A R
Appendix A — target torque values
Hardware
size
Hardware style
Min. torque
ft-lbs.
Max. torque
ft-lbs.
Target torque
ft-lbs.
4-40
Slotted head
0.42
0.5
0.42
6-32
Slotted head
0.75
0.92
0.83
8-32
Slotted head
1.3
1.5
1.42
10-32
Phillips head
3.12
3.33
3.25
10-32
Self-tapping
5.83
6.67
6.25
1/4-20
Self-tapping 0.104" matl. thickness
8
11
10
1/4-20
Self-tapping 0.119" matl. thickness
13
16
15
1/4-20
Carriage bolt
10
11
11
1/4-20
Hex head
10
11
11
5/16-18
Hex head
17
20
19
3/8-16
Carriage bolt
35
38
37
3/8-16
Hex head
17
20
19
3/8-16
Flange bolt
35
38
37
3/8-16
Flange bolt (for stand-off insulators)
33
35
34
3/8-16
Threaded stud
18
20
19
3/8-16
Fiberglass threaded stud
10
12
11
1/2-13
Hex head
55
62
59
5/8-11
Hex head
35
40
38
End of life of product
ABB products are manufactured to meet or
exceed the standards of compliance for quality
and environmental management systems in
accordance with ISO 9001 and ISO 14001. All of
these items can be supplied with a certificate
of quality.
Methods of disposal
Disposal can be carried out in a manner of ways
depending upon the material of the product.
Below is the recommended method of disposal
for various raw materials.
The duty of ABB is to facilitate subsequent
recycling or disposal at the end of product life.
During disposal of the product, it is always
necessary to act in accordance with local legal
requirements in force.
Raw material
Recommended method of disposal
Metal material (Fe, Cu, Al, Ag, Zn, W, etc.)
Separation and recycling
Thermoplasts
Recycling or disposal
Epoxy resin
Separation of metal and disposal of remains
Rubber
Disposal
Oil (transformer oil)
Draining and recycling or proper disposal
SF6 gas
Discharging from equipment
Packing material
Recycling or disposal
—
Maintenance
Содержание ReliaGear ND
Страница 2: ......