14.3.3
Setting guidelines
GUID-0D5A517C-1F92-46B9-AC2D-F41ED4E7C39E v1
GUID-52BF4E8E-0B0C-4F75-99C4-0BCB22CDD166 v2
The parameters for Fuse failure supervision VDSPVC are set via the local HMI or
PCM600.
GUID-0B298162-C939-47E4-A89B-7E6BD7BEBB2C v2
The voltage input type (phase-to-phase or phase-to-neutral) is selected using
ConTypeMain
and
ConTypePilot
parameters, for main and pilot fuse groups
respectively.
The connection type for the main and the pilot fuse groups must be
consistent.
The settings
Ud>MainBlock
,
Ud>PilotAlarm
and
USealIn
are in percentage of the
base voltage,
UBase
. Set
UBase
to the primary rated phase-to-phase voltage of the
potential voltage transformer.
UBase
is available in the Global Base Value groups;
the particular Global Base Value group, that is used by VDSPVC, is set by the
setting parameter
GlobalBaseSel
.
The settings
Ud>MainBlock
and
Ud>PilotAlarm
should be set low (approximately
30% of
UBase
) so that they are sensitive to the fault on the voltage measurement
circuit, since the voltage on both sides are equal in the healthy condition. If
U
SetPrim
is the desired pick up primary phase-to-phase voltage of measured fuse group, the
setting of
Ud>MainBlock
and
Ud>PilotAlarm
will be given according to equation
>
or
>
100
S etPrim
Base
U
Ud MainBlock Ud PilotAlarm
U
=
×
IECEQUATION2424 V2 EN-US
(Equation 533)
U
SetPrim
is defined as phase to neutral or phase to phase voltage dependent of the
selected
ConTypeMain
and
ConTypePilot
. If
ConTypeMain
and
ConTypePilot
are
set to
Ph-N
than the function performs internally the rescaling of
U
SetPrim
.
When
SealIn
is set to
On
and the fuse failure has last for more than 5 seconds, the
blocked protection functions will remain blocked until normal voltage conditions
are restored above the
USealIn
setting. The fuse failure outputs are deactivated
when the normal voltage conditions are restored.
Section 14
1MRK 506 369-UEN B
Secondary system supervision
594
Line distance protection REL670 2.2 IEC
Application manual
Содержание REL670 2.2 IEC
Страница 1: ...RELION 670 SERIES Line distance protection REL670 Version 2 2 IEC Application manual ...
Страница 2: ......
Страница 32: ...26 ...
Страница 70: ...64 ...
Страница 110: ...104 ...
Страница 152: ...146 ...
Страница 564: ...558 ...
Страница 570: ...564 ...
Страница 592: ...586 ...
Страница 706: ...700 ...
Страница 804: ...798 ...
Страница 848: ...842 ...
Страница 860: ...854 ...
Страница 882: ...876 ...
Страница 896: ...890 ...
Страница 906: ...900 ...
Страница 907: ...901 ...