The second part of a complete Power swing logic (PSLPSCH) functionality is a
blocking and tripping logic for evolving power swings, see figure
. The simplified logic is presented in figure
operation of the underreaching distance protection zone (Zone 1) at power swings,
caused by the faults and their clearance on the adjacent power lines. The logic
should generally be configured between distance protection zones 1 and 2.
Configuration
SEMOD131360-60 v2
The fault impedance should be detected within the external boundary of Power
Swing Detection (ZMRPSB) function without power swing detected during the
entire fault duration. Configure for this reason the STZMPSD to the functional
output signal of ZMRPSB function, which indicates the measured impedance
within its external boundaries.
STZML
BLOCK
&
STMZH
STZMPSD
STPSD
t
tDZ
t
tZL
&
>1
&
&
&
-loop
>1
STZMLL
BLKZMH
&
en06000237.vsd
IEC06000237 V1 EN-US
Figure 229:
Blocking and tripping logic for evolving power swings
No system oscillation should be detected in power system. Configure for this
reason the STPSD functional input to the START functional output of ZMRPSB
function or to any binary input signal indicating the detected oscillations within the
power system.
Configure the functional input STZMUR to the start output of the instantaneous
underreaching distance protection zone (usually START of distance protection zone
1). The function will determine whether the start signal of this zone is permitted to
be used in further logic or not, dependent on time difference on appearance of
overreaching distance protection zone (usually zone 2).
Configure for this reason the functional output signal STZMURPS to the start
output of the overreaching distance protection zone (usually START of distance
protection zone 2).
Section 8
1MRK 506 369-UEN B
Impedance protection
422
Line distance protection REL670 2.2 IEC
Application manual
Содержание REL670 2.2 IEC
Страница 1: ...RELION 670 SERIES Line distance protection REL670 Version 2 2 IEC Application manual ...
Страница 2: ......
Страница 32: ...26 ...
Страница 70: ...64 ...
Страница 110: ...104 ...
Страница 152: ...146 ...
Страница 564: ...558 ...
Страница 570: ...564 ...
Страница 592: ...586 ...
Страница 706: ...700 ...
Страница 804: ...798 ...
Страница 848: ...842 ...
Страница 860: ...854 ...
Страница 882: ...876 ...
Страница 896: ...890 ...
Страница 906: ...900 ...
Страница 907: ...901 ...