IEC140000131-1-en
IEC140000131 V1 EN-US
Figure 45:
3PHSUM setting parameters example-showing that 3PHSUM is
using the External DFT reference coming indirectly from SMAI3
Figure
shows an example of wrong connection of 3PHSUM and
PHASORREPORT blocks in ACT where SMAI3 is configured as the reference
block for DFT reference external out (DFTRefExtOut) and 3PHSUM uses external
DFT reference (from SMAI3).
IEC140000132-2-en.vsd
IEC140000132 V2 EN-US
Figure 46:
An example of wrong connection of 3PHSUM and
PHASORREPORT blocks in ACT
If settings for PMUREPORT instances (PHASORREPORT1 instances 1 and 2
above) differ for SvcClass or ReportRate, then the synchrophasor reported by
PHASOR2 connection from PHASORREPORT1 instance 2 will not be compliant
with IEEE C37.118 standard. The reason is as in the rule 2, the filtering in SMAI/
3PHSUM block is adapted according to the performance class (SvcClass) and
reporting rate of the connected instance of PHASORREPORT function block. On
the other hand, when 3PHSUM uses external DFT reference, it also adapts its
filtering according to the SMAI reference block. Therefore, in order to avoid two
1MRK 506 369-UEN B
Section 6
Wide area measurement system
Line distance protection REL670 2.2 IEC
123
Application manual
Содержание REL670 2.2 IEC
Страница 1: ...RELION 670 SERIES Line distance protection REL670 Version 2 2 IEC Application manual ...
Страница 2: ......
Страница 32: ...26 ...
Страница 70: ...64 ...
Страница 110: ...104 ...
Страница 152: ...146 ...
Страница 564: ...558 ...
Страница 570: ...564 ...
Страница 592: ...586 ...
Страница 706: ...700 ...
Страница 804: ...798 ...
Страница 848: ...842 ...
Страница 860: ...854 ...
Страница 882: ...876 ...
Страница 896: ...890 ...
Страница 906: ...900 ...
Страница 907: ...901 ...