16.5.3
Function block
IEC10000249-1-en.vsd
GOOSEDPRCV
BLOCK
^DPOUT
DATAVALID
COMMVALID
TEST
IEC10000249 V1 EN
Figure 338:
GOOSEDPRCV function block
16.5.4
Signals
Table 551:
GOOSEDPRCV Input signals
Name
Type
Default
Description
BLOCK
BOOLEAN
0
Block of function
Table 552:
GOOSEDPRCV Output signals
Name
Type
Description
DPOUT
INTEGER
Double point output
DATAVALID
BOOLEAN
Data valid for double point output
COMMVALID
BOOLEAN
Communication valid for double point output
TEST
BOOLEAN
Test output
16.5.5
Settings
Table 553:
GOOSEDPRCV Non group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
Operation
Disabled
Enabled
-
-
Disabled
Operation Enable/Disable
16.5.6
Operation principle
The DATAVALID output will be HIGH if the incoming message is with valid data.
The COMMVALID output will become LOW when the sending IED is under total failure
condition and the GOOSE transmission from the sending IED does not happen.
The TEST output will go HIGH if the sending IED is in test mode.
Section 16
1MRK 506 335-UUS A
Station communication
726
Technical manual
Содержание REL650 series
Страница 1: ...Relion 650 series Line distance protection REL650 ANSI Technical manual ...
Страница 2: ......
Страница 42: ...36 ...
Страница 48: ...42 ...
Страница 58: ...52 ...
Страница 68: ...62 ...
Страница 74: ...68 ...
Страница 194: ...188 ...
Страница 534: ...528 ...
Страница 580: ...574 ...
Страница 722: ...716 ...
Страница 792: ...786 ...
Страница 855: ...849 ...