14.18.5
Settings
Table 512:
SSCBR Non group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
Operation
Off
On
-
-
On
Operation Off / On
AccDisLevel
5.00 - 500.00
A
0.01
10.00
RMS current setting below which energy
accumulation stops
CurrExp
0.00 - 2.00
-
0.01
2.00
Current exponent setting for energy calculation
RatedFaultCurr
500.00 - 75000.00
A
0.01
5000.00
Rated fault current of the breaker
RatedOpCurr
100.00 - 5000.00
A
0.01
1000.00
Rated operating current of the breaker
AccCurrAlmLvl
0.00 - 20000.00
-
0.01
2500.00
Setting of alarm level for accumulated currents
power
AccCurrLO
0.00 - 20000.00
-
0.01
2500.00
Lockout limit setting for accumulated currents
power
DirCoef
-3.00 - -0.50
-
0.01
-1.50
Directional coefficient for CB life calculation
LifeAlmLevel
0 - 99999
-
1
5000
Alarm level for CB remaining life
OpNumRatCurr
1 - 99999
-
1
10000
Number of operations possible at rated current
OpNumFaultCurr
1 - 10000
-
1
1000
Number of operations possible at rated fault
current
OpNumAlm
0 - 9999
-
1
200
Alarm limit for number of operations
OpNumLO
0 - 9999
-
1
300
Lockout limit for number of operations
tOpenAlm
0 - 200
ms
1
40
Alarm level setting for open travel time
tCloseAlm
0 - 200
ms
1
40
Alarm level setting for close travel time
OpenTimeCorr
0 - 100
ms
1
10
Correction factor for open travel time
CloseTimeCorr
0 - 100
ms
1
10
Correction factor for CB close travel time
DifTimeCorr
-10 - 10
ms
1
5
Correction factor for time difference in auxiliary
and main contacts open time
tSprngChrgAlm
0.00 - 60.00
s
0.01
1.00
Setting of alarm for spring charging time
tPressAlm
0.00 - 60.00
s
0.01
0.10
Time delay for gas pressure alarm
TPressLO
0.00 - 60.00
s
0.01
0.10
Time delay for gas pressure lockout
AccEnerInitVal
0.00 - 9999.99
-
0.01
0.00
Accumulation energy initial value
CountInitVal
0 - 9999
-
1
0
Operation numbers counter initialization value
CBRemLife
0 - 9999
-
1
5000
Initial value for the CB remaining life estimates
InactDayAlm
0 - 9999
Day
1
2000
Alarm limit value of the inactive days counter
InactDayInit
0 - 9999
Day
1
0
Initial value of the inactive days counter
InactHourAlm
0 - 23
Hour
1
0
Alarm time of the inactive days counter in hours
1MRK 506 335-UUS A
Section 14
Monitoring
683
Technical manual
Содержание REL650 series
Страница 1: ...Relion 650 series Line distance protection REL650 ANSI Technical manual ...
Страница 2: ......
Страница 42: ...36 ...
Страница 48: ...42 ...
Страница 58: ...52 ...
Страница 68: ...62 ...
Страница 74: ...68 ...
Страница 194: ...188 ...
Страница 534: ...528 ...
Страница 580: ...574 ...
Страница 722: ...716 ...
Страница 792: ...786 ...
Страница 855: ...849 ...