Name of OUTx
Type
Description
Value when
activated
Value when
deactivated
OUT1
BOOLEAN
Output 1
1
0
OUT2
BOOLEAN
Output 2
2
0
OUT3
BOOLEAN
Output 3
4
0
OUT4
BOOLEAN
Output 4
8
0
OUT5
BOOLEAN
Output 5
16
0
OUT6
BOOLEAN
Output 6
32
0
OUT7
BOOLEAN
Output 7
64
0
OUT8
BOOLEAN
Output 8
128
0
OUT9
BOOLEAN
Output 9
256
0
OUT10
BOOLEAN
Output 10
512
0
OUT11
BOOLEAN
Output 11
1024
0
OUT12
BOOLEAN
Output 12
2048
0
OUT13
BOOLEAN
Output 13
4096
0
OUT14
BOOLEAN
Output 14
8192
0
OUT15
BOOLEAN
Output 15
16384
0
OUT16
BOOLEAN
Output 16
32768
0
The sum of the numbers in column “Value when activated” when all OUTx (where x = 1
to 16) are active that is=1; is 65535. 65535 is the highest integer that can be converted by
the IB16A function block.
13.9
Integer to boolean 16 conversion with logic node
representation IB16FCVB
13.9.1
Identification
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Integer to boolean 16 conversion with
logic node representation
IB16FCVB
-
-
13.9.2
Functionality
Integer to boolean conversion with logic node representation function IB16FCVB is used
to transform an integer to 16 binary (logic) signals.
Section 13
1MRK 506 335-UUS A
Logic
566
Technical manual
Содержание REL650 series
Страница 1: ...Relion 650 series Line distance protection REL650 ANSI Technical manual ...
Страница 2: ......
Страница 42: ...36 ...
Страница 48: ...42 ...
Страница 58: ...52 ...
Страница 68: ...62 ...
Страница 74: ...68 ...
Страница 194: ...188 ...
Страница 534: ...528 ...
Страница 580: ...574 ...
Страница 722: ...716 ...
Страница 792: ...786 ...
Страница 855: ...849 ...