AND
OR
AND
S
AND
0
0-tUnsucCl
AND
OR
ANSI10000263-1-en.vsd
initiate
block start
UnsucClByCBchk = CBcheck
UNSUCCL
shot 0
Pulse STBRREC
(Closing)
52a
CBclosed
R
ANSI10000263 V1 EN
Figure 182:
Issue of signal UNSUCCL, unsuccessful reclosing
11.3.6.10
Automatic continuation of the reclosing sequence
The auto-reclosing function can be programmed to proceed to the following reclosing
shots (if selected) even if the initiate signals are not received from the protection functions,
but the breaker is still not closed. This is done by setting parameter
AutoCont
=
Enabled
and
tAutoContWait
to the required delay for the function to proceed without a new
initiate.
Section 11
1MRK 506 335-UUS A
Control
386
Technical manual