From logic for
reclosing
programs
AND
AND
OR
AND
"STBRREC (79) Open time"
timer
PULSE
Blocking out
CBREADY
initiate
SYNC
3PT4TO
3PT3TO
3PT2TO
3PT1TO
OR
AND
OR
INPROGR
Inhibit (internal)
Blocking out
INHIBIT
Pulse STBRREC (79) (above)
ANSI10000256-2-en=.vsd
3PT5TO
Reset Timer On
0
CL
COUNTER
Shot 0
R
1
2
3
4
5
Shot 1
Shot 2
Shot 3
Shot 4
Shot 5
LOGIC
reclosing
programs
3PT1
3PT2
3PT3
OR
Shot 0
Shot 1
Shot 2
Shot 3
Shot 4
Shot 5
3PT4
3PT5
3PT1TO
STBRREC (79)
State Control
1PT1
OR
1PT1
TR3P
initiate
pickup
PREP3P
0
0-t1 3Ph
0
0-tSync
0
0-tReset
0-tInhibit
0
ANSI10000256 V3 EN
Figure 178:
Auto-reclosing Disabled/Enabled and start
11.3.6.3
Auto-reclosing mode selection
The Auto-reclosing mode is selected with setting
ARMode
=
3 phase (0)
,
1/3ph (1)
,
1ph
(2)
,
1ph+1*3ph (4)
.
The following integers shall be used.
1=3phase
,
2=1/3ph
,
3=1ph
or
5=1ph+1*3ph
.
1MRK 506 335-UUS A
Section 11
Control
381
Technical manual