10.2.7
Operation principle
10.2.7.1
Zero and negative sequence detection
The zero and negative sequence function continuously measures the currents and voltages
in all three phases and calculates: (see figure
•
the zero-sequence voltage 3V
0
•
the zero-sequence current 3I
0
•
the negative sequence current 3I
2
•
the negative sequence voltage 3V
2
The measured signals are compared with their respective set values
3V0PU
and
3I0PU
,
3V2PU
and
3I2PU.
The function enable the internal signal FuseFailDetZeroSeq if the measured zero-
sequence voltage is higher than the set value
3V0PU
and the measured zero-sequence
current is below the set value
3I0PU
.
The function enable the internal signal FuseFailDetNegSeq if the measured negative
sequence voltage is higher than the set value
3V2PU
and the measured negative sequence
current is below the set value
3I2PU
.
A drop off delay of 100 ms for the measured zero-sequence and negative sequence current
will prevent a false fuse failure detection at un-equal breaker opening at the two line ends.
Section 10
1MRK 506 335-UUS A
Secondary system supervision
336
Technical manual