![ABB REL650 series Скачать руководство пользователя страница 254](http://html1.mh-extra.com/html/abb/rel650-series/rel650-series_applications-manual_3479164254.webp)
7.15.3
Directional underpower protection GUPPDUP (37)
7.15.3.1
Identification
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Directional underpower protection
GUPPDUP
P <
2
SYMBOL-LL V2 EN
37
7.15.3.2
Setting guidelines
GlobalBaseSel
: Selects the global base value group used by the function to define (
IBase
),
(
VBase
) and (
SBase
).
Operation
: With the parameter
Operation
the function can be set
Enabled
/
Disabled
.
Mode
: The voltage and current used for the power measurement. The setting possibilities
are shown in table
.
For reverse power applications
PosSeq
or
Arone
modes are strongly recommended.
Table 15:
Complex power calculation
Set value
Mode
Formula used for complex power calculation
A, B, C
*
*
*
A
A
B
B
C
C
S V
I
V
I
V
I
=
×
+
×
+
×
EQUATION2055-ANSI V1 EN
(Equation 153)
Arone
*
*
AB
A
BC
C
S V
I
V
I
=
×
-
×
EQUATION2056-ANSI V1 EN
(Equation 154)
PosSeq
*
3
PosSeq
PosSeq
S
V
I
= ×
×
EQUATION2057-ANSI V1 EN
(Equation 155)
AB
*
*
(
)
AB
A
B
S V
I
I
=
×
-
EQUATION2058-ANSI V1 EN
(Equation 156)
BC
*
*
(
)
BC
B
C
S V
I
I
=
×
-
EQUATION2059-ANSI V1 EN
(Equation 157)
Table continues on next page
Section 7
1MRK 506 334-UUS A
Current protection
248
Application manual
Содержание REL650 series
Страница 1: ...Relion 650 series Line distance protection REL650 ANSI Application manual...
Страница 2: ......
Страница 30: ...24...
Страница 99: ...IED IED ANSI05000460 V2 EN 1MRK 506 334 UUS A Section 4 Analog inputs 93 Application manual...
Страница 110: ...104...
Страница 260: ...254...
Страница 274: ...268...
Страница 280: ...274...
Страница 396: ...390...
Страница 494: ...488...
Страница 506: ...500...
Страница 515: ...509...