Quick Start Guide For The DNP Orion To ABB REL 356 Relays Using Modbus

8

8.

 

The ORION unit allows the operator to configure the unit by connecting an IBM compatible PC RS
232 port via a cable.  Attach the RS 232 cable to the ORION DIAGNOSTIC PORT as shown in Figure
2, illustration 7 or Figure 2A illustration 7 depending upon unit selected.

9.

 

SOFTWARE CONFIGURATION:  Supplied with the unit is a diskette with a file “ CTL2MOD.exe”.
This file configures the point mapping for the  Conitel C300 to  Modbus conversion.  The  Conitel
information varies from the format of  Modbus and therefore the mapping of the two dissimilar
protocol’s points must occur.  Place the file into  the a directory within the personal computer.  TYPE
“CTL2MOD” and depress the “ENTER KEY”.

10.

 

Use the arrow keys to scroll to the “Setup” Menu.  Select the  submenu  titled PC –Prot  Conv.  The
following menu shall appear.  Select the parameters as shown.  The Port selection, however should
be modified to match your computer systems hardware configuration.  After selection of all
parameters, simultaneously depress the “CONTROL and ENTER” key on the configuration terminal’s
keyboard.

+--------------¦ NovaTech Conitel-Modbus Configuration Program ¦---------------+
¦ PRINTER: READY                                       FILE NAME:     TEST.CTL ¦
¦ File   Setup   Memory Map   Transfer   About                        10:37:06 ¦
¦¦¦¦¦¦¦¦¦+------------------------+¦¦¦¦¦¦¦¦¦¦¦¦¦¦¦¦¦¦¦¦¦¦¦¦¦¦¦¦¦¦¦¦¦¦¦¦¦¦¦¦¦¦¦¦¦
¦¦¦¦¦¦¦¦¦¦ +-----------¦ Local PC Communication Setup ¦------------+¦¦¦¦¦¦¦¦¦¦¦¦
¦¦¦¦¦¦¦¦¦¦ ¦                                                       ¦¦¦¦¦¦¦¦¦¦¦¦¦
¦¦¦¦¦¦¦¦¦¦ ¦  Port      Baud Rate   Parity   Data Bits   Stop Bits ¦¦¦¦¦¦¦¦¦¦¦¦¦
¦¦¦¦¦¦¦¦¦+-¦  (¦)COM1   ( )300      (¦)NONE  ( )6        (¦)1      ¦¦¦¦¦¦¦¦¦¦¦¦¦
¦¦¦¦¦¦¦¦¦¦¦¦  ( )COM2   ( )600      ( )ODD   ( )7        ( )2      ¦¦¦¦¦¦¦¦¦¦¦¦¦
¦+---------¦            ( )1200     ( )EVEN  (¦)8                  ¦----------+¦
¦¦Current V¦            ( )2400                                    ¦          ¦¦
¦¦         ¦            ( )4800                                    ¦          ¦¦
¦¦         ¦            (¦)9600                                    ¦          ¦¦
¦¦         ¦            ( )19200                                   ¦          ¦¦
¦¦         ¦                                                       ¦          ¦¦
¦¦         ¦                                                       ¦          ¦¦
¦¦         ¦                                                       ¦          ¦¦
¦¦         +-------------------------------------------------------+          ¦¦
¦¦                                                                            ¦¦
¦¦                                                                            ¦¦
¦¦                                                                            ¦¦
¦¦                                                                            ¦¦
¦+-----------------------------¦ Message Window ¦-----------------------------+¦
+------------------------------------------------------------------------------+
 <Tab>: Next Field  <Esc>: Abort  <Ctrl>+<Enter>: Accept

Figure 8 – Local PC Communication Setup Screen For The Orion DIAG Port.

11.

 

With the “SETUP” parameter highlighted, select the  ProtConv  Modbus Setup submenu selection,
until the following screen is displayed.  The parameters listed in Figure 5 match those in the
protective device configuration  (Step 7). After selection of all parameters, simultaneously depress the
“CONTROL and ENTER” key on the configuration terminal’s keyboard.

www 

. ElectricalPartManuals 

. com

Содержание REL 356

Страница 1: ...Diskette 1 It is imperative to realize that the ORION is available in two formats a 19 rack mount version and a Table Top version Please refer to the appropriate diagrams when using this guide Apply p...

Страница 2: ...st to the ORION SCADA MASTER RS 232 port with a 9 pin D shell connector The cable end should mate with the ORION s male connector The unit is a DTE pinout and a custom cable may have to be developed f...

Страница 3: ...hld IED 55 56 57 58 59 60 61 RS 485 AUX COM Isolated Port Shield Bare Wire Relay Pin 55 to Orion Terminal B TX RX Relay Pin 56 to Orion Terminal A TX RX Relay Pin 57 to Orion Terminal Shld Ground Illu...

Страница 4: ...tor termination Breakouts of each of the jumper locations are shown in Illustration 1 and Illustration 2 The position of the jumpers in the open or closed positions are highlighted FOR AN ORION TABLE...

Страница 5: ...cation through the AUX COM PORT Its location is shown in Figure 2 illustration 6 and Illustration 5 or Illustration 2 depending upon the physical connection type or Figure 2A illustration 5 Connect th...

Страница 6: ...uide For The DNP Orion To ABB REL 356 Relays Using Modbus 6 Figure 4 PC Port Menu Selection VI A Comset Figure 5 MODBUS PONI M Configuration Menu Presentation w w w E l e c t r i c a l P a r t M a n u...

Страница 7: ...ion RS 485 To Modbus PONI PONI M Port E C NORMAL FAIL PICKUP RECLOSEROUT SYSTEM RESET T I M E INSTANTANEOUS FREQUENCY NEGATIVE SEQUENCE TARGET RESET STATUS T A R G E T S A B C N DPU 2000R Network Part...

Страница 8: ...Select the parameters as shown The Port selection however should be modified to match your computer systems hardware configuration After selection of all parameters simultaneously depress the CONTROL...

Страница 9: ...select the PROTCONV CONITEL Setup submenu selection until the following screen is displayed The parameters listed in Figure 6 match those in the CONITEL Host After selection of all parameters simultan...

Страница 10: ...everal choices is displayed Select the ADD INPUTS selection NovaTech Conitel Modbus Configuration Program PRINTER READY FILE NAME TEST CTL File Setup Memory Map Transfer About 10 37 30 Standard Add In...

Страница 11: ...AME TEST CTL File Setup Memory Map Transfer About 10 38 33 Standard Modbus Conitel Input Conitel Data Type AI Point Description Analog Input 1 Conitel Group 1 Conitel Point Start 1 Number of Conitel P...

Страница 12: ...US CONITEL OFF ADDR 1 MODBUS OFF 1 TOGGLE CONITEL PORT DISPLAY CURRENTLY OFF 2 TOGGLE MODBUS PORT DISPLAY CURRENTLY OFF M MODEM SETUP and TEST MENU S DISPLAY COMMUNICATION STATISTICS Please enter your...

Страница 13: ...menu Step 10 Figure 4 4 The ORION Amber CONFIG LED flashes A The ORION has not been configured Download the saved configuration file from the configuration terminal Step 15 Figure 9 5 Communication d...

Страница 14: ...istors are configured in the IED protective relay Jumpers J6 termination J8 Pullup and J7 Pulldown Step 6 9 Communications Strings are not visible when the RUN MMI and submenu 1 Toggle DNP 3 0 Port Di...

Страница 15: ...Jumpers J6 termination J8 Pullup and J7 Pulldown Step 6 Optional Information The RS 232 Cables and RS 485 Cable diagrams are included below for reference ORION RS 232 C CABLE Personal Computer OR ORIO...

Страница 16: ...ardType 8 Card MODBUS EMULATION COM 3 DB9 Female DB 9 Male to Phoenix Connector Adapter Assembly 1 TX RX 2 TX RX 7 Common REL 356 PONI END UNIT INSTALL TERMINATION RESISTOR 120 OHMS J 15 Closed A B Sh...

Отзывы: