
16
1MRS 751055-MUM
Directional or Non-Directional Earth-Fault Relay
Operator’s Manual
REJ 527
)LJ $ODUP
The non-latching operation mode selected, the operation indication disappears along
with the fault. When the indication is selected to be latching, it remains even if the
fault disappears. Reset latching indications as follows:
• To clear the alarm text and indication LEDs, press the [C] button. If the fault has
disappeared, the message will be cleared; if not, the fault is stable and the alarm
text will remain on the display.
If several protection functions trip within a short time, the indication of the first
tripping remains on the display until the time determined by the “New trip
indication” setting value has expired. After this, a new trip indication displaces the
old one.
3.2.2.6.
Self-supervision, IRF
When the self-supervision system detects a permanent internal relay fault, the ready
indication LED starts blinking. At the same time the IRF relay that is normally
picked up drops off and a fault code appears on the display. During an internal fault
all other output contacts are blocked.
)LJ ,QWHUQDOIDXOW
The fault code is a number that identifies the fault type. Record the code and state it
when ordering service. Fault codes are listed in the following table.
Alarm527
C
E
START
READY
TRIP
ALARM
Io>
Iob & Uo
Table 3.2.2.6-1
Fault codes
Fault code
Type of fault
4
No response on output contact test, PO1
5
No response on output contact test, PO2
6
No response on output contact test, SO1
7
No response on output contact test, SO2
30
Faulty program memory
Faultc
C
E
START
READY
TRIP
INTERNAL FAULT
FAULT CODE :56