1MRS 752137-MUM
Combined Overcurrent and Earth-Fault Relay
Operator’s Manual
REJ 525
19
To alter a parameter, proceed as follows:
1. Select the main menu group “CONFIGURATION” and enter the desired
parameter using the arrow buttons.
2. Enter the setting mode by pressing the [E] button. If the default password has
been replaced, the text “PASSWORD” will appear on the display demanding a
password. If the default password “999” is still valid, no password will be
required.
3. The text or the first digit of the setting value of the parameter to be edited will
start to flash. Set the digit/character using the [
↑
] and [
↓
] buttons. The next digit/
character to be set is activated by pressing the [
→
] or [
←
] button (when setting
an enumerator, however, the left and right arrows have no function).
4. To store a new value and return the display to the view mode, press the [E]
button. If the parameter is of a numerical kind, the display will confirm the
storage by once flashing “---” on the display.
5. To exit the setting mode without saving changes, press the [C] button once
before confirming and the display will be returned to the view mode.
6. Press the [C] button once more and the display will be returned to the idle mode.
)LJ 6HW0,SDVVZRUG
If a setting value beyond the allowed limits is confirmed in the setting mode, the
former value will be restored.
3.2.3.4.
How to acknowledge and reset indications, output contacts and
memorized values
• To clear the LEDs and the display, press the [C] button. The LEDs and the
display will be cleared only if the fault situation has disappeared.
• Press the [C] button for at least five seconds to unlatch the output contacts. Note
that the LEDs and the display have to be cleared before this.
• Press the [C] and [E] buttons simultaneously for at least half a second to perform
a master reset, i.e. to clear indications and memorized values and to unlatch the
output contacts. The display being inverted confirms this action. Memorized
values include recorded data, disturbance recorder data and average values.
Setp
ar
E
C
Confirm
Cancel
Parameter Menu
CONFIGURATION
PASSWORD HMI :xxx
Содержание REJ 525
Страница 1: ...REJ 525 Combined Overcurrent and Earth Fault Relay Operator s Manual ...
Страница 2: ......
Страница 38: ......
Страница 39: ......