-3U
0
=U
ref
Operate area
Instrument
transformer
angle error
3I
0
(prim)
3I
0
(to prot)
a
Characteristic after
angle compensation
RCAcomp
en06000651.vsd
RCADir
= 0º
IEC06000651 V2 EN
Figure 16:
Explanation of RCAcomp
Operation mode 3I
0
· 3U
0
· cosφ
1.
Set the polarizing voltage to 1.2 ·
UNRel>
and the phase angle between voltage
and current to the set characteristic angle (
RCADir
), the current lagging the
voltage.
2.
Measure that the operate power is equal to the
SN>
setting for the set directional
element.
Note that for operation, both the injected current and voltage must be greater
than the set values
INRel>
and
UNRel>
respectively.
The function activates the START and STDIRIN outputs.
3.
Measure with angles
j
=
RCADir
+/- 45° that the measuring element operates
when 3I
0
· 3U
0
· cos (
RCADir
-
j
) = 3I0 · 3U0 · cos(+/-45) =
SN>
.
4.
Compare the result with the set value. Take the set characteristic into
consideration, see figure
5.
Measure the operate time of the timer by injecting 1.2 ·
UNRel>
and a current to
get two times the set
SN>
operate value.
Section 6
1MRK 502 049-UEN A
Testing functionality
64
Commissioning manual
Содержание REG650 ANSI
Страница 1: ...Relion 650 series Generator protection REG650 Commissioning manual...
Страница 2: ......
Страница 8: ......
Страница 20: ...12...
Страница 40: ...32...
Страница 42: ...34...
Страница 50: ...42...
Страница 120: ...112...
Страница 126: ...118...
Страница 142: ...134...
Страница 143: ...135...