ABB
10
GUID-89A9F7DF-FB82-4E8D-B449-7C0BB51C1DCA V1 EN
1MDB07207-YN
Feeder Protection
REF601
Product version: 2.0
Table 12. Electromagnetic compatibility tests
Description
Type test value
Reference
1 MHz burst disturbance test:
IEC 61000-4-12
IEC 60255-22-1, class III
2.5 kV, 1MHz, 400 pulses/sec
1.0 kV, 1MHz, 400 pulses/sec
• Common mode
• Differential mode
Electrostatic discharge test:
IEC 60255-22-2, class III
8 kV, 150 pF/330
Ω
• Air discharge
Radio frequency, electro-magnetic
IEC 60255-22-3, class III
10 V/m
field immunity test:
Fast transient disturbance tests:
IEC 60255-22-4, class A
4 kV, 5.0 kHz
• All ports
Surge immunity test:
IEC 60255-22-5
IEC 61000-4-5
1.0 kV, 1.2/50 μs
0.5 kV, 1.2/50 μs
• Common mode
• Differential mode
Immunity to conducted disturbance
IEC 61000-4-8
100 A/m
1000 A/m
• Continuous
• Short duration ( 1 sec )
induced by RF:
Conducted radio frequency
IEC 60255-22-6, class III
f=150 KHz...80 Mhz
10 V
Pulse magnetic field immunity tests:
IEC 61000-4-9
1000 A/m, 6.4/16
μ
s
IEC 61000-4-2
6 kV, 150 pF/330
Ω
• Contact discharge
10 V/m
f=80-1000 MHz
f=80, 160, 450, 900 MHz
IEC 61000-4-3
interferene tests:
IEC 61000-4-4
IEC 61000-4-6
Содержание REF601
Страница 21: ......