A051355
Fig. 14.2.-1
Binary outputs commissioning page
14.3.
Analog input commissioning page
This page shows the analog measurements acquired by the analog input module.
The shown values are independent on the rated primary current or voltage of the
primary sensors. The measurements are reported in absolute values taking into
consideration as nominal values of the secondary windings 1 Amp and 100 V. If the
5 Amp current inputs are connected applying the nominal rated current, it will be
shown 1 A.
48
REF 542plus
REF 542plus
Multifunction Protection and Switchgear Control Unit
Operator's manual
1MRS755869