R
X
RFFwPE
1
3
5
2
4
ArgNegRes
85%
50% of
RLdFw
6
IEC09000734-4-en.vsd
7
60°
)
/
(
loop
W
)
/
(
loop
W
)
1
(
XN
X
+
IEC09000734 V4 EN-US
Figure 25:
Operating characteristic for phase selection function, forward
direction single-phase faults
Table 22:
Test points for phase-to-earth loop L3-E (Ohm/loop)
Test point
Reach
Value
Comments
1
X
[X1+XN]
XN=(X
0
-X
1
)/3
R
0
2
X
0
R
RLdFw
When RLdFW < RFFwPE
R
RFFwPE
When RLdFwPE > RFFwPE
3
X
0.85·[X1+XN]
R≈0.491·(X1+XN)+RFFwPE
R
0.85·[X1+XN]·1/tan(60°)+RFFwPE
4
X
0.85·[X1+XN]
Can be limited by RFFwPE
R
-0.85·[X1+XN]·
tan (AngNegRes-90°)
5
X
RFFwPE·tan (ArgLd)
Only when RLdFw < RFFwPE
R
RFFwPE
6
X
-0.5·RLdFw·tan (ArgDir)
R
0.5·RLdFw
Table
1MRK 505 378-UEN A
Section 11
Testing functionality by secondary injection
Line differential protection RED670 2.2 IEC
119
Commissioning manual
Содержание RED670 Relion 670 series
Страница 1: ...RELION 670 SERIES Line differential protection RED670 Version 2 2 IEC Commissioning manual ...
Страница 2: ......
Страница 18: ...12 ...
Страница 36: ...30 ...
Страница 68: ...62 ...
Страница 72: ...66 ...
Страница 108: ...102 ...
Страница 278: ...272 ...
Страница 282: ...276 ...
Страница 288: ...282 ...
Страница 306: ...300 ...
Страница 307: ...301 ...