Voltage-restrained time overcurrent protection VRPVOC

Voltage-restrained time overcurrent protection (VRPVOC)
function can be used as generator backup protection against
short-circuits.

The overcurrent protection feature has a settable current level
that can be used either with definite time or inverse time
characteristic. Additionally, it can be voltage controlled/
restrained.

One undervoltage step with definite time characteristic is also
available within the function in order to provide functionality for
overcurrent protection with undervoltage seal-in.

9.  Secondary system supervision

Current circuit supervision CCSSPVC

Open or short circuited current transformer cores can cause
unwanted operation of many protection functions such as
differential, earth-fault current and negative-sequence current
functions.

Current circuit supervision (CCSSPVC) compares the residual
current from a three phase set of current transformer cores with
the neutral point current on a separate input taken from another
set of cores on the current transformer.

A detection of a difference indicates a fault in the circuit and is
used as alarm or to block protection functions expected to give
inadvertent tripping.

Fuse failure supervision FUFSPVC

The aim of the fuse failure supervision function FUFSPVC is to
block voltage measuring functions at failures in the secondary
circuits between the voltage transformer and the IED in order to
avoid inadvertent operations that otherwise might occur.

The fuse failure supervision function basically has three different
detection methods, negative sequence and zero sequence
based detection and an additional delta voltage and delta
current detection.

The negative sequence detection algorithm is recommended
for IEDs used in isolated or high-impedance earthed networks.
It is based on the negative-sequence quantities.

The zero sequence detection is recommended for IEDs used in
directly or low impedance earthed networks. It is based on the
zero sequence measuring quantities.

The selection of different operation modes is possible by a
setting parameter in order to take into account the particular
earthing of the network.

A criterion based on delta current and delta voltage
measurements can be added to the fuse failure supervision
function in order to detect a three phase fuse failure, which in

practice is more associated with voltage transformer switching
during station operations.

Fuse failure supervision VDSPVC

Different protection functions within the protection IED
operates on the basis of measured voltage at the relay point.
Some example of protection functions are:

• Distance protection function.
• Undervoltage function.
• Energisation function and voltage check for the weak

infeed logic.

These functions can operate unintentionally, if a fault occurs in
the secondary circuits between voltage instrument
transformers and the IED. These unintentional operations can
be prevented by VDSPVC.

VDSPVC is designed to detect fuse failures or faults in voltage
measurement circuit, based on phase wise comparison of
voltages of main and pilot fused circuits. VDSPVC blocking
output can be configured to block functions that need to be
blocked in case of faults in the voltage circuit.

Multipurpose filter SMAIHPAC

The multi-purpose filter function block, SMAIHPAC, is arranged
as a three-phase filter. It has very much the same user interface
(e.g. inputs and outputs) as the standard pre-processing
function block SMAI. However the main difference is that it can
be used to extract any frequency component from the input
signal. Thus it can, for example, be used to build sub-
synchronous resonance protection for synchronous generator.

10.  Control

Synchrocheck, energizing check, and synchronizing SESRSYN

The Synchronizing function allows closing of asynchronous
networks at the correct moment including the breaker closing
time, which improves the network stability.

Synchrocheck, energizing check, and synchronizing SESRSYN
function checks that the voltages on both sides of the circuit
breaker are in synchronism, or with at least one side dead to
ensure that closing can be done safely.

SESRSYN function includes a built-in voltage selection scheme
for double bus and 1½ breaker or ring busbar arrangements.

Manual closing as well as automatic reclosing can be checked
by the function and can have different settings.

For systems, which are running asynchronous, a synchronizing
function is provided. The main purpose of the synchronizing
function is to provide controlled closing of circuit breakers when
two asynchronous systems are going to be connected. The
synchronizing function evaluates voltage difference, phase
angle difference, slip frequency and frequency rate of change
before issuing a controlled closing of the circuit breaker.
Breaker closing time is a parameter setting.

1MRK 505 346-BEN -

Line differential protection RED670 2.1 IEC

 

Product version: 2.1

 
 

ABB

33

Содержание RED670 Relion 670 series

Страница 1: ...Relion 670 series Line differential protection RED670 2 1 IEC Product guide...

Страница 2: ...chnical data 47 22 Ordering for customized IED 116 23 Ordering for pre configured IED 126 24 Ordering for Accessories 132 Disclaimer The information in this document is subject to change without notic...

Страница 3: ...es The Disturbance recorder will also show remote station currents as received to this IED time compensated with measure communication time Out of Step function is available to separate power system s...

Страница 4: ...e been defined for following applications Single breaker double or single bus with three phase tripping A31 Single breaker double or single bus with single phase tripping A32 Multi breaker one and a h...

Страница 5: ...F PIOC 50N IN GOP PDOP 32 P HZ PDIF 87 Id L6C PDIF 87L 3Id I STB PTOC 50STB 3I STB S SIMG 63 LT3C PDIF 87LT 3Id I LT6C PDIS 87LT 3Id I SA PTOF 81 f SA PTUF 81 f GUP PDUP 37 P ZMM PDIS 21 Z ZMH PDIS 21...

Страница 6: ...GOP PDOP 32 P HZ PDIF 87 Id L6C PDIF 87L 3Id I STB PTOC 50STB 3I STB S SIMG 63 LT3C PDIF 87LT 3Id I LT6C PDIS 87LT 3Id I SA PTOF 81 f SA PTUF 81 f GUP PDUP 37 P ZMM PDIS 21 Z ZMH PDIS 21 Z ZMQ PDIS 2...

Страница 7: ...0 VDC PTOV 60 Ud STB PTOC 50STB 3I STB CCS SPVC 87 INd I Q CBAY 3 Control FDPS PDIS 21 FMPS PDIS 21 EF4 PTOC 51N_67N 4 IN CV GAPC 2 I U VD SPVC 60 Ud ZD RDIR 21 Z _ SDE PSDE 67N IN ZMH PDIS 21 Z HZ PD...

Страница 8: ...0STB 3I STB CCS SPVC 87 INd I Q CBAY 3 Control FDPS PDIS 21 FMPS PDIS 21 EF4 PTOC 51N_67N 4 IN CV GAPC 2 I U VD SPVC 60 Ud ZD RDIR 21 Z _ SDE PSDE 67N IN ZMH PDIS 21 Z HZ PDIF 87 Id NS4 PTOC 46I2 4 I2...

Страница 9: ...ns Table 1 Example of quantities 2 number of basic instances 0 3 option quantities 3 A03 optional function included in packages A03 refer to ordering details 1MRK 505 346 BEN Line differential protect...

Страница 10: ...B16 ZDSRDIR 21D Directional impedance quadrilateral including series compensation 0 2 1 B16 1 B16 1 B16 1 B16 FDPSPDIS 21 Phase selection quadrilateral characteristic with fixed angle 0 2 1 B11 1 B16...

Страница 11: ...1 1 B22 1 B22 1 B22 1 B22 OOSPPAM 78 Out of step protection 0 1 1 B22 1 B22 1 B22 1 B22 ZCVPSOF Automatic switch onto fault logic voltage and current based 0 1 1 B11 1 B16 1 B17 1 B11 1 B16 1 B17 1 B...

Страница 12: ...F Breaker failure protection 0 2 1 2 1 2 STBPTOC 50STB Stub protection 0 2 1 B11 1B 1 B11 1 B11 1B 1 B11 CCPDSC 52PD Pole discordance protection 0 2 1 2 1 2 GUPPDUP 37 Directional underpower protectio...

Страница 13: ...A32 RED670 B32 Multipurpose protection CVGAPC General current and voltage protection 0 4 4 F01 4 F01 4 F01 4 F01 General calculation SMAIHPAC Multipurpose filter 0 6 1 67 requires voltage 2 67N requi...

Страница 14: ...als 5 5 5 5 5 AUTOBITS AutomationBits command function for DNP3 0 3 3 3 3 3 SINGLECMD Single command 16 signals 4 4 4 4 4 I103CMD Function commands for IEC 60870 5 103 1 1 1 1 1 I103GENCMD Function co...

Страница 15: ...nteger conversion 18 18 18 18 18 BTIGAPC Boolean 16 to Integer conversion with Logic Node representation 16 16 16 16 16 IB16 Integer to Boolean 16 conversion 18 18 18 18 18 ITBGAPC Integer to Boolean...

Страница 16: ...13 6 M15 LMBRFLO Fault locator 1 1 1 1 1 I103MEAS Measurands for IEC 60870 5 103 1 1 1 1 1 I103MEASUSR Measurands user defined signals for IEC 60870 5 103 3 3 3 3 3 I103AR Function status auto reclose...

Страница 17: ...e logic blocks Q T Total number of instances ANDQT 120 INDCOMBSPQT 20 INDEXTSPQT 20 INVALIDQT 22 INVERTERQT 120 ORQT 120 PULSETIMERQT 40 RSMEMORYQT 40 SRMEMORYQT 40 TIMERSETQT 40 XORQT 40 Table 4 Tota...

Страница 18: ...MST1TCP MST2TCP MST3TCP MST4TCP DNP3 0 for serial communication protocol 1 1 1 1 1 DNPFREC DNP3 0 fault records for TCP IP and EIA 485 communication protocol 1 1 1 1 1 IEC 61850 8 1 Parameter setting...

Страница 19: ...3 1 P03 1 P03 1 P03 Remote communication Binary signal transfer receive transmit 6 36 6 36 6 36 6 36 6 36 Transmission of analog data from LDCM 1 1 1 1 1 Receive binary status from remote LDCM 6 3 3 6...

Страница 20: ...uts SMMI Signal matrix for mA inputs SMAI1 SMAI12 Signal matrix for analog inputs ATHSTAT Authority status ATHCHCK Authority check AUTHMAN Authority management FTPACCS FTP access with password SPACOMM...

Страница 21: ...ternal series resistor and a voltage dependent resistor which are both mounted externally to the IED are also required The external resistor unit shall be ordered under IED accessories in the Product...

Страница 22: ...nnel Comm Channel IEC05000040 V2 EN Figure 7 Example of application on a three terminal line with 1 breaker arrangements The current differential algorithm provides high sensitivity for internal fault...

Страница 23: ...alog signal transfer for line differential protection The line differential protection function can be arranged as a master master system or a master slave system alternatively In the former current s...

Страница 24: ...t increases the security of protection during the high impedance fault conditions Low voltage criterion takes the phase voltages and phase to phase voltages as inputs It increases the security of prot...

Страница 25: ...encroachment function activated The independent measurement of impedance for each fault loop together with a sensitive and reliable built in phase selection makes the function suitable in application...

Страница 26: ...onal forward or reverse or non directional mode offset This makes them suitable together with different communication schemes for the protection of power lines and cables in complex network configurat...

Страница 27: ...pendent zones Individual settings for each zone in resistive and reactive reach gives flexibility for use as back up protection for transformer connected to overhead lines and cables of different type...

Страница 28: ...ltage reversal Each measurement zone is designed with the flexibility to operate in either quadrilateral or mho characteristic mode This can even be decided separate for the phase to ground or phase t...

Страница 29: ...perate first Two current channels I3P1 and I3P2 are available in OOSPPAM function to allow the direct connection of two groups of three phase currents that may be needed for very powerful generators w...

Страница 30: ...acity There is also available one nondirectional 3I0 step and one 3U0 overvoltage tripping step No specific sensitive current input is needed SDEPSDE can be set as low 0 25 of IBase Thermal overload p...

Страница 31: ...otection with undervoltage seal in 6 Voltage protection Two step undervoltage protection UV2PTUV Undervoltages can occur in the power system during faults or abnormal conditions Two step undervoltage...

Страница 32: ...ges to be connected For information about how to connect analog inputs refer to Application manual IED application Analog inputs Setting guidelines Overfrequency protection SAPTOF Overfrequency protec...

Страница 33: ...e associated with voltage transformer switching during station operations Fuse failure supervision VDSPVC Different protection functions within the protection IED operates on the basis of measured vol...

Страница 34: ...material damage and or accidental human injury Each apparatus control function has interlocking modules included for different switchyard arrangements where each function handles interlocking of one...

Страница 35: ...eady with a settable pulse time AutomationBits command function for DNP3 0 AUTOBITS AutomationBits function for DNP3 AUTOBITS is used within PCM600 to get into the configuration of the commands coming...

Страница 36: ...rrent protection the directional residual overcurrent protection can be supported with a logic that uses communication channels In the directional scheme information of the fault current direction mus...

Страница 37: ...components are present in all types of fault condition Negative sequence voltage and current get high values during unsymmetrical faults Zero sequence overvoltage protection LCZSPTOV Zero sequence co...

Страница 38: ...resets or returns to the state it had before the power interruption The SET input has priority TIMERSET function has pick up and drop out delayed outputs related to the input signal The timer has a se...

Страница 39: ...nd on the Substation automation system about measured voltages currents frequency active reactive and apparent power and power factor measured analog values from merging units primary phasors positive...

Страница 40: ...and reliable information about disturbances in the power system It facilitates understanding system behavior and related primary and secondary equipment during and after a disturbance Recorded informa...

Страница 41: ...4UFCNT The 30 limit counter L4UFCNT provides a settable counter with four independent limits where the number of positive and or negative flanks on the input signal are counted against the setting val...

Страница 42: ...r equipment either on the Substation Automation SA bus or Substation Monitoring SM bus Available communication protocols are IEC 61850 8 1 communication protocol IEC 61850 9 2LE communication protocol...

Страница 43: ...standard format is used Galvanic X 21 line data communication module X 21 LDCM A module with built in galvanic X 21 converter which e g can be connected to modems for pilot wires is also available Ga...

Страница 44: ...e connection uses the same signal for RX and TX and is a multidrop communication with no dedicated Master or slave This variant requires however a control of the output The 4 wire connection has separ...

Страница 45: ...0 316 0 12 4 228 6 9 00 6U 1 1 x 19 265 9 10 47 448 3 17 65 242 1 9 53 255 8 10 07 430 3 16 86 190 5 7 50 428 3 16 86 465 1 18 31 228 6 9 00 482 6 19 00 The H and K dimensions are defined by the 19 ra...

Страница 46: ...ustomized products Connection diagram 670 series 2 11MRK002801 AF Connection diagrams for Configured products Connection diagram RED670 2 1 A31 1MRK002803 HA Connection diagram RED670 2 1 B31 1MRK0028...

Страница 47: ...range Current Ir 1 or 5 A 0 2 40 Ir Operative range 0 100 x Ir Permissive overload 4 Ir cont 100 Ir for 1 s Burden 150 mVA at Ir 5 A 20 mVA at Ir 1 A Ac voltage Ur 110 V 0 5 288 V Operative range 0 34...

Страница 48: ...C D for IEC 61850 9 2LE IEEE C37 118 Standard IEEE 802 3u 100BASE FX Type of fiber 62 5 125 mm multimode fibre Wave length 1300 nm Optical connector Type ST Communication speed Fast Ethernet 100 Mbit...

Страница 49: ...ly with influencing factors within nominal range Table 13 BIM Binary input module with enhanced pulse counting capabilities Quantity Rated value Nominal range Binary inputs 16 DC voltage RL 24 30 V 48...

Страница 50: ...dard IEC 61810 2 Function or quantity Trip and signal relays Fast signal relays parallel reed relay Binary outputs 10 2 Max system voltage 250 V AC DC 250 V DC Test voltage across open contact 1 min 1...

Страница 51: ...250 V 8 0 A 250 V 8 0 A Breaking capacity for DC with L R 40 ms 48 V 1 A 110 V 0 4 A 220 V 0 2 A 250 V 0 15 A 48 V 1 A 110 V 0 4 A 220 V 0 2 A 250 V 0 15 A Maximum capacitive load 10 nF Table 17 SOM S...

Страница 52: ...nal relays Binary outputs 24 Max system voltage 250 V AC DC Test voltage across open contact 1 min 1000 V rms Current carrying capacity Per relay continuous Per relay 1 s Per process connector pin con...

Страница 53: ...ndence on Within nominal range Influence Frequency dependence operate value fr 2 5 Hz for 50 Hz fr 3 0 Hz for 60 Hz 1 0 Hz Frequency dependence for distance protection operate value fr 2 5 Hz for 50 H...

Страница 54: ...A Power frequency immunity test 150 300 V 50 Hz IEC 60255 26 Zone A Conducted common mode immunity test 15 Hz 150 kHz IEC 61000 4 16 Class IV Power frequency magnetic field test 1000 A m 3 s 100 A m...

Страница 55: ...93 IEC 60068 2 78 Damp heat test cyclic Test Db for 6 cycles at 25 to 55 C and humidity 93 to 95 1 cycle 24 hours IEC 60068 2 30 Table 26 CE compliance Test According to Immunity EN 60255 26 Emissivit...

Страница 56: ...g 60 0 of fundamental hidden setting 1 0 of Ir Table 29 1Ph High impedance differential protection HZPDIF Function Range or value Accuracy Operate voltage 10 900 V I U R 1 0 of Ir at I Ir 1 0 of I at...

Страница 57: ...and table 173 Critical impulse time 2ms typically at 0 to 10 x Id Charging current compensation On Off LT3CPDIF and LT6CPDIF Operate time restrained function at 0 to 10 x Id Min 25 ms Max 35 ms Reset...

Страница 58: ...0 5 of Ur Independent time delay zero sequence current at 0 to 2 x Iset 0 000 60 000 s 0 2 or 40 ms whichever is greater Independent time delay low current operation at 2 x Iset to 0 0 000 60 000 s 0...

Страница 59: ...Ir Angle at 0 degrees and 85 degrees Positive sequence resistance 0 01 1000 00 phase Zero sequence reactance 0 10 9000 00 phase Zero sequence resistance 0 01 3000 00 phase Fault resistance phase to ea...

Страница 60: ...er is greater Operate time 25 ms typically IEC 60255 121 Reset ratio 105 typically Reset time at 0 1 to 2 x Zreach Min 20 ms Max 35 ms Table 34 Phase selection quadrilateral characteristic with fixed...

Страница 61: ...lly Reset time at 0 5 to 1 5 x Zreach Min 30 ms Max 45 ms Table 36 Full scheme distance protection quadrilateral for earth faults ZMMPDIS Function Range or value Accuracy Number of zones Max 5 with se...

Страница 62: ...se Positive sequence reactance 0 10 3000 00 phase 2 0 static accuracy 2 0 degrees static angular accuracy Conditions Voltage range 0 1 1 1 x Ur Current range 0 5 30 x Ir Angle at 0 degrees and 85 degr...

Страница 63: ...speed distance protection ZMFPDIS ZMFCPDIS Function Range or value Accuracy Number of zones 3 selectable directions 3 fixed directions Minimum operate current Ph Ph and Ph E 5 6000 of IBase 1 0 of Ir...

Страница 64: ...00 9000 00 l Dynamic overreach 5 at 85 deg measured with CVT s and 0 5 SIR 30 Definite time delay to trip Ph E and Ph Ph operation 0 000 60 000 s 0 2 or 35 ms whichever is greater Operate time 16 ms t...

Страница 65: ...wer swings 0 000 60 0000 s 0 2 or 15 ms whichever is greater Timer for blocking the overreaching zones trip 0 000 60 0000 s 0 2 or 15 ms whichever is greater Table 44 Pole slip protection PSPPPAM Func...

Страница 66: ...lay for residual voltage at 1 2 to 0 8 x Uset 0 000 60 000 s 0 2 or 25 ms whichever is greater Operating mode No Filter NoPref Cyclic 1231c 1321c Acyclic 123a 132a 213a 231a 312a 321a Table 47 Automat...

Страница 67: ...te time at 0 to 2 x Iset Min 15 ms Max 25 ms Reset time at 2 to 0 x Iset Min 15 ms Max 25 ms Critical impulse time 10 ms typically at 0 to 2 x Iset Operate time at 0 to 10 x Iset Min 5ms Max 15ms Rese...

Страница 68: ...start non directional at 0 to 2 x Iset Min 15 ms Max 30 ms Reset time start non directional at 2 to 0 x Iset Min 15 ms Max 30 ms Operate time start non directional at 0 to 10 x Iset Min 5 ms Max 20 ms...

Страница 69: ...d Table 173 16 curve types See Table 171 Table 172 and Table 173 Second harmonic blocking 5 100 of fundamental 2 0 of Ir Minimum polarizing voltage 1 100 of UBase 0 5 of Ur Minimum polarizing current...

Страница 70: ...for directional release 1 100 of IBase For RCA 60 degrees 2 5 of Ir at I Ir 2 5 of I at I Ir Minimum polarizing voltage 1 100 of UBase 0 5 of Ur Minimum polarizing current 2 100 of IBase 1 0 of Ir Rea...

Страница 71: ...5 of U at U Ur Operate time for non directional residual overcurrent at 0 to 2 x Iset Min 40 ms Max 65 ms Reset time for non directional residual overcurrent at 2 to 0 x Iset Min 40 ms Max 65 ms Opera...

Страница 72: ...rrent 5 200 of lBase 1 0 of Ir at I Ir 1 0 of I at I Ir Reset ratio phase current 95 Operate residual current 2 200 of lBase 1 0 of Ir at I Ir 1 0 of I at I Ir Reset ratio residual current 95 Phase cu...

Страница 73: ...Range or value Accuracy Power level for Step 1 and Step 2 0 0 500 0 of SBase 1 0 of Sr at S Sr 1 0 of S at S Sr where 1 732 r r r S U I Characteristic angle for Step 1 and Step 2 180 0 180 0 degrees...

Страница 74: ...ent 1 0 of Ir Independent operate time delay 0 000 60 000 s 0 2 or 45 ms whichever is greater Independent reset time delay 0 010 60 000 s 0 2 or 30 ms whichever is greater Start time at current change...

Страница 75: ...2 or 40ms whichever is greater Definite time delay step 2 at 1 2 to 0 x Uset 0 000 60 000 s 0 2 or 40ms whichever is greater Minimum operate time inverse characteristics 0 000 60 000 s 0 5 or 40ms whi...

Страница 76: ...te time start at 0 to 1 2 x Uset Min 20 ms Max 35 ms Reset time start at 1 2 to 0 x Uset Min 5 ms Max 25 ms Critical impulse time 10 ms typically at 0 to 2 x Uset Impulse margin time 15 ms typically T...

Страница 77: ...tion 0 000 60 000 s 0 2 or 35 ms whichever is greater Operate time delay when disconnecting all three phases 0 000 60 000 s 0 2 or 35 ms whichever is greater Time delay to block when all three phase v...

Страница 78: ...UMin 50 150 of Ubase Exponent 0 0 5 0 tMax 0 010 60 000 s tMin 0 010 60 000 s 1 0 or 120 ms whichever is greater Exponent U UMin t tMax tMin tMin UNom UMin EQUATION1182 V1 EN Equation 3 U Umeasured T...

Страница 79: ...requency 45 00 65 00 Hz 2 0 mHz Definite restore time delay 0 000 60 000 s 0 2 or 100 ms whichever is greater Definite time delay for frequency gradient trip 0 200 60 000 s 0 2 or 120 ms whichever is...

Страница 80: ...er is greater Overcurrent non directional Start time at 0 to 2 x Iset Min 15 ms Max 30 ms Reset time at 2 to 0 x Iset Min 15 ms Max 30 ms Start time at 0 to 10 x Iset Min 5 ms Max 20 ms Reset time at...

Страница 81: ...operation step 1 2 1 0 200 0 of UBase 1 0 of Ur at U Ur 1 0 of U at U Ur Directional function Settable NonDir forward and reverse Relay characteristic angle 180 to 180 degrees 2 0 degrees Relay operat...

Страница 82: ...voltage 120 or 230 V 50 60 Hz Operate earth fault resistance value Approx 1 20 k Influence of harmonics in the DC field voltage Negligible influence of 50 V 150 Hz or 50 V 300 Hz Permitted leakage ca...

Страница 83: ...Minimum operate time for inverse time characteristics 0 00 60 00 s 0 2 or 35 ms whichever is greater High voltage limit voltage dependent operation 30 0 100 0 of UBase 1 0 of Ur Start undervoltage 2 0...

Страница 84: ...equence 1 100 of IBase 0 5 of Ir Operate voltage negative sequence 1 100 of UBase 0 5 of Ur Operate current negative sequence 1 100 of IBase 0 5 of Ir Operate voltage change level 1 100 of UBase 10 0...

Страница 85: ...n 5 ms Max 15 ms Reset time block of main fuse failure at 0 to 1 x Ur Min 15 ms Max 30 ms Operate value alarm for pilot fuse failure 10 0 80 0 of UBase 0 5 of Ur Reset ratio 110 Operate time alarm for...

Страница 86: ...mHz Breaker closing pulse duration 0 050 60 000 s 0 2 or 15 ms whichever is greater tMaxSynch which resets synchronizing function if no close has been made before set time 0 000 6000 00 s 0 2 or 35 ms...

Страница 87: ...r Maximum operate pulse duration 0 000 60 000 s 0 2 or 15 ms whichever is greater Reclaim time 0 00 6000 00 s 0 2 or 15 ms whichever is greater Circuit breaker closing pulse length 0 000 60 000 s 0 2...

Страница 88: ...on logic for distance protection ZC1PPSCH Function Range or value Accuracy Scheme type Intertrip Permissive UR Permissive OR Blocking Co ordination time for blocking communication scheme 0 000 60 000...

Страница 89: ...residual overcurrent protection ECRWPSCH Function Range or value Accuracy Operate mode of WEI logic Off Echo Echo Trip Operate voltage 3U0 for WEI trip 5 70 of UBase 0 5 of Ur Operate time for current...

Страница 90: ...tical impulse time undervoltage 10 ms typically at 1 2 to 0 8x Uset Impulse margin time undervoltage 15 ms typically Operate value overvoltage 1 200 of UBase 0 5 of Ur at U Ur 0 5 of U at U Ur Critica...

Страница 91: ...0 to 1 2 x Uset 0 000 120 000 s 0 2 or 40 ms whichever is greater Table 88 Zero sequence overvoltage protection LCZSPTOV Function Range or value Accuracy Operate value zero sequence overvoltage 1 200...

Страница 92: ...60 000 s 0 2 or 35 ms whichever is greater Transient overreach start function 5 at 100 ms Table 90 Zero sequence overcurrent protection LCZSPTOC Function Range or value Accuracy Operate value zero seq...

Страница 93: ...to operate at 0 to 2 x Iset 0 000 60 000 s 0 2 or 30 ms whichever is greater Table 92 Three phase undercurrent LCP3PTUC Function Range or value Accuracy Operate value undercurrent 1 00 100 00 of IBase...

Страница 94: ...C instances Function Quantity with cycle time 3 ms 8 ms 100 ms TMAGAPC 6 6 Table 96 Number of ALMCALH instances Function Quantity with cycle time 3 ms 8 ms 100 ms ALMCALH 5 Table 97 Number of WRNCALH...

Страница 95: ...PULSETIMER 10 10 20 0 000 90000 000 s 0 5 10 ms Table 105 Number of RSMEMORY instances Logic block Quantity with cycle time 3 ms 8 ms 100 ms RSMEMORY 10 10 20 Table 106 Number of SRMEMORY instances Lo...

Страница 96: ...s 8 ms 100 ms INVALIDQT 6 6 Table 113 Number of INVERTERQT instances Logic block Quantity with cycle time 3 ms 8 ms 100 ms INVERTERQT 20 100 Table 114 Number of ORQT instances Logic block Quantity wit...

Страница 97: ...00 ms XORQT 10 30 Table 120 Number of instances in the extension logic package Logic block Quantity with cycle time 3 ms 8 ms 100 ms AND 40 40 100 GATE 49 INV 40 40 100 LLD 49 OR 40 40 100 PULSETIMER...

Страница 98: ...chever is greater 8 0 999999 9 s 0 2 or 100 ms whichever is greater 100 0 999999 9 s 0 2 or 250 ms whichever is greater Table 126 Number of TEIGAPC instances Function Quantity with cycle time 3 ms 8 m...

Страница 99: ...t power S 10 to 300 V 0 1 4 0 x Ir 0 5 of Sr at S 0 5 x Sr 0 5 of S at S 0 5 x Sr 100 to 220 V 0 5 2 0 x Ir 0 2 of S Power factor cos 10 to 300 V 0 1 4 0 x Ir 0 02 100 to 220 V 0 5 2 0 x Ir 0 01 Table...

Страница 100: ...nction Range or value Accuracy Voltage positive sequence U1 10 to 300 V 0 5 of U at U 50 V 0 2 of U at U 50 V Voltage zero sequence 3U0 10 to 300 V 0 5 of U at U 50 V 0 2 of U at U 50 V Voltage negati...

Страница 101: ...Hz Sampling rate 1 kHz at 50 Hz 1 2 kHz at 60 Hz Recording bandwidth 5 300 Hz Table 137 Insulation gas monitoring function SSIMG Function Range or value Accuracy Pressure alarm level 1 00 100 00 10 0...

Страница 102: ...Alarm level for open and close travel time 0 200 ms 3 ms Alarm level for number of operations 0 9999 Independent time delay for spring charging time alarm 0 00 60 00 s 0 2 or 30 ms whichever is greate...

Страница 103: ...mum number of analog inputs 30 Maximum number of disturbance reports 100 Table 145 Disturbance recorder Function Value Buffer capacity Maximum number of analog inputs 40 Maximum number of binary input...

Страница 104: ...dule BIM Cycle time for report of counter value 1 3600 s Table 148 Energy metering ETPMMTR Function Range or value Accuracy Energy metering kWh Export Import kvarh Export Import Input from MMXU No ext...

Страница 105: ...e Protocol LON Communication speed 1 25 Mbit s Table 152 SPA communication protocol Function Value Protocol SPA Communication speed 300 1200 2400 4800 9600 19200 or 38400 Bd Slave number 1 to 899 Tabl...

Страница 106: ...ity Range or value Connector X 21 Micro D sub 15 pole male 1 27 mm 0 050 pitch Connector ground selection 2 pole screw terminal Standard CCITT X21 Communication speed 64 kbit s Insulation 1 kV Maximum...

Страница 107: ...about 2 km 1 mile 22 dB typical distance 80 km 50 mile 26 dB typical distance 110 km 68 mile Optical connector Type ST Type FC PC Type FC PC Protocol C37 94 C37 94 implementation C37 94 implementation...

Страница 108: ...t occasionally a temporary conductivity caused by condensation is to be expected Connection system Table 164 CT and VT circuit connectors Connector type Rated voltage and current Maximum conductor are...

Страница 109: ...ble 168 GPS time synchronization module GTM Function Range or value Accuracy Receiver 1 s relative UTC Time to reliable time reference with antenna in new position or after power loss longer than 1 mo...

Страница 110: ...low level high level 1 3 Vpp 3 x low level max 9 Vpp Supported formats IRIG B 00x IRIG B 12x Accuracy 10 s for IRIG B 00x and 100 s for IRIG B 12x Input impedance 100 k ohm Optical connector Optical c...

Страница 111: ...or 40 ms whichever is greater ANSI Extremely Inverse A 28 2 B 0 1217 P 2 0 tr 29 1 ANSI Very inverse A 19 61 B 0 491 P 2 0 tr 21 6 ANSI Normal Inverse A 0 0086 B 0 0185 P 0 02 tr 0 46 ANSI Moderately...

Страница 112: ...k I CR EQUATION1253 SMALL V1 EN I Imeasured Iset k 0 05 999 in steps of 0 01 A 0 005 200 000 in steps of 0 001 B 0 00 20 00 in steps of 0 01 C 0 1 10 0 in steps of 0 1 P 0 005 3 000 in steps of 0 001...

Страница 113: ...1437 SMALL V2 EN k 0 05 1 10 in steps of 0 01 Type C curve 3 0 480 32 0 5 0 035 t k U U U EQUATION1438 SMALL V2 EN k 0 05 1 10 in steps of 0 01 Programmable curve P k A t D U U B C U EQUATION1439 SMAL...

Страница 114: ...055 32 0 5 k t U U U EQUATION1432 SMALL V1 EN U Uset U Umeasured k 0 05 1 10 in steps of 0 01 Programmable curve P k A t D U U B C U EQUATION1433 SMALL V1 EN U Uset U Umeasured k 0 05 1 10 in steps o...

Страница 115: ...TION1437 SMALL V2 EN k 0 05 1 10 in steps of 0 01 Type C curve 3 0 480 32 0 5 0 035 t k U U U EQUATION1438 SMALL V2 EN k 0 05 1 10 in steps of 0 01 Programmable curve P k A t D U U B C U EQUATION1439...

Страница 116: ...erential protection RED670 2 1 X00 A 0 0 0 0 0 0 0 Impedance protection B 0 0 0 0 Current protection C 00 0 00 1 0 0 0 0 0 Voltage protection Frequency protection Multipurpose protection General calcu...

Страница 117: ...ordered Line differential protection 6 CT sets 3 5 line ends L6CPDIF 1MRK005904 NB 11 0 1 Line differential protection 3 CT sets with inzone transformers 2 3 line ends LT3CPDIF 1MRK005904 PB 12 0 1 Li...

Страница 118: ...tive 4 Distance protection quadrilateral with separate settings for PP and PE Directional impedance quadrilateral ZDRDIR 1MRK005907 BA 2 0 2 Distance protection zone quadrilateral characteristic separ...

Страница 119: ...rent protection VRPVOC 1MRK005910 XA 21 0 3 Table 187 Voltage protection Position 1 2 3 4 5 6 7 8 D 0 1 Table 188 Voltage functions Function Function identification Ordering no Positi on Available qty...

Страница 120: ...5 0 1 Note Only one Apparatus control can be ordered Apparatus control for single bay max 15 app 2CBs incl Interlocking APC15 1MRK005917 BY 6 0 1 Table 199 Scheme communication Position 1 2 3 4 5 6 7...

Страница 121: ...unction identification Ordering no Position Available qty Selected qty Notes and rules Process Bus communication IEC 61850 9 2 1MRK005930 TA 1 0 if F00 is selected 6 if N00 is selected Note RED670 cus...

Страница 122: ...seal F Selected Table 210 Connection type for Power supply module Selection Notes and Rules Compression terminals M Ringlug terminals N Auxiliary power supply Power supply module 24 60 VDC A Power su...

Страница 123: ...A 100 220V 50 60Hz 4 Second TRM 5I 1A 4I 5A 3U 100 220V 50 60Hz 5 Second TRM 6I 6U 1A 100 220V 50 60Hz 6 Second TRM 6I 6U 5A 100 220V 50 60Hz 7 Second TRM 6I 1A 50 60Hz 8 Maximum qty 1 Second TRM 6I 5...

Страница 124: ...F F F F F F F F F F F F F BIMp 16 inputs RL48 60 VDC 30 mA for pulse counting G G G G G G G G G G G G G G BIMp 16 inputs RL110 125 VDC 30 mA for pulse counting H H H H H H H H H H H H H H BIM 16 input...

Страница 125: ...h 2 TRM No remote communication board included X X X X X X Optical short range LDCM A A A A A A Max 4 LDCM same or different type can be selected Always place LDCM modules on the same board to support...

Страница 126: ...0 DAB1RGN1N1XXXXXXX AXFXXX AX Using the code of each position 1 13 specified as RED670 1 2 2 3 3 3 3 3 3 3 3 3 3 3 3 3 4 4 5 6 7 8 9 10 10 10 10 110 11 11 11 11 11 11 11 11 11 11 12 12 12 12 12 12 13...

Страница 127: ...ional distance protection with phase selection B 28 Directional distance protection with phase selection series compensation B 29 Out of step protection B 22 Sensitive directional residual overcurrent...

Страница 128: ...rack mounting kit for 1 1 x 19 case C Wall mounting kit D Note Wall mounting not recommended with communication modules with fibre connection SLM OEM LDCM Flush mounting kit E Flush mounting kit IP54...

Страница 129: ...nals B Second TRM 9I 3U 1A 110 220V 3 Second TRM 9I 3U 5A 110 220V 4 Second TRM 5I 1A 4I 5A 3U 110 220V 5 Second TRM 6I 6U 1A 110 220V 6 Second TRM 6I 6U 5A 110 220V 7 Second TRM 6I 1A 110 220V 8 Seco...

Страница 130: ...ng F F F F F F F F F F F F BIMp 16 inputs RL48 60 VDC 30 mA for pulse counting G G G G G G G G G G G G BIMp 16 inputs RL110 125 VDC 30 mA for pulse counting H H H H H H H H H H H H BIM 16 inputs RL220...

Страница 131: ...Always place LDCM modules on the same board to support redundant communication in P30 2 and P30 3 P31 2 and P31 3 or P32 2 and P32 3 Optical medium range LDCM 1310 nm B B B B B B Optical long range L...

Страница 132: ...umber RK926 315 AK Single breaker Single or Three Phase trip with external neutral on current circuits ordering number RK926 315 AC Multi breaker Single or Three Phase trip with internal neutral on cu...

Страница 133: ...antity 1MRK 000 611 A Note To connect the key switch leads with 10 A Combiflex socket on one end must be used Mounting kit Ordering number Side by side mounting kit Quantity 1MRK 002 420 Z Configurati...

Страница 134: ...IEC 61850 Edition 2 IEC Quantity 1MRK 511 350 UEN Communication protocol manual IEC 60870 5 103 IEC Quantity 1MRK 511 351 UEN Communication protocol manual LON IEC Quantity 1MRK 511 352 UEN Communica...

Страница 135: ...ment numbers Operation manual IEC 1MRK 500 123 UEN ANSI 1MRK 500 123 UUS Engineering manual IEC 1MRK 511 355 UEN ANSI 1MRK 511 355 UUS Installation manual IEC 1MRK 514 024 UEN ANSI 1MRK 514 024 UUS Co...

Страница 136: ...136...

Страница 137: ...act us ABB AB Substation Automation Products SE 721 59 V ster s Sweden Phone 46 0 21 32 50 00 Fax 46 0 21 14 69 18 www abb com substationautomation 1MRK 505 346 BEN Copyright 2015 ABB All rights reser...

Отзывы: