PID-3909-INPUTSIGNALS v9
Table 91:
LFPTTR Input signals
Name
Type
Default
Description
I3P
GROUP
SIGNAL
-
Group signal for current input
BLOCK
BOOLEAN
0
Block of function
BLKTR
BOOLEAN
0
Block of trip
ENMULT
BOOLEAN
0
Current multiplyer used when THOL is for two or
more lines
AMBTEMP
REAL
0
Ambient temperature from external temperature
sensor
SENSFLT
BOOLEAN
0
Validity status of ambient temperature sensor
RESET
BOOLEAN
0
Reset of internal thermal load counter
PID-3908-OUTPUTSIGNALS v7
Table 92:
LCPTTR Output signals
Name
Type
Description
TRIP
BOOLEAN
Trip
START
BOOLEAN
Start Signal
ALARM
BOOLEAN
Alarm signal
LOCKOUT
BOOLEAN
Lockout signal
PID-3909-OUTPUTSIGNALS v8
Table 93:
LFPTTR Output signals
Name
Type
Description
TRIP
BOOLEAN
Trip
START
BOOLEAN
Start Signal
ALARM
BOOLEAN
Alarm signal
LOCKOUT
BOOLEAN
Lockout signal
8.5.5
Settings
PID-3908-SETTINGS v7
Table 94:
LCPTTR Group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
Operation
Off
On
-
-
Off
Operation Off / On
TRef
0 - 300
Deg C
1
90
End temperature rise above ambient of
the line when loaded with IRef
IRef
0 - 400
%IB
1
100
The load current (in % of IBase) leading
to TRef temperature
IMult
1 - 5
-
1
1
Current multiplier when function is used
for two or more lines
Table continues on next page
Section 8
1MRK 505 394-UEN A
Current protection
206
Line differential protection RED650 2.2 IEC
Technical manual
Содержание RED650
Страница 1: ...RELION 650 SERIES Line differential protection RED650 Version 2 2 Technical manual...
Страница 2: ......
Страница 36: ...30...
Страница 46: ...40...
Страница 232: ...226...
Страница 272: ...266...
Страница 288: ...282...
Страница 306: ...300...
Страница 406: ...400...
Страница 436: ...430...
Страница 502: ...496...
Страница 614: ...608...
Страница 628: ...622...
Страница 644: ...638...
Страница 760: ...754...
Страница 778: ...772...
Страница 814: ...808...
Страница 870: ...864...
Страница 874: ...868...
Страница 924: ...918...
Страница 925: ...919...