E. Troubleshooting
Ensure that breaker is installed correctly and all
terminal connections are torqued per instructions.
If the breaker fails to close check:
1.
2.
3.
4.
5.
For overload and short circuit on the system.
Handle position - TRIPPED - reset by moving
handle fully to OFF position and then to the ON
position, see Figure 4.
Undervoltage trip is supplied with rated
voltage.
Shunt trip is de-energized and no trip signal
exists
Breaker trip unit settings are properly adjusted.
Installation instruction
references:DEH40324 –
Auxiliary switch & bell alarms.
DEH40363 – Undervoltage
release & shunt trip modules
DEH40532 – Terminal lugs.
Optional inter-
phase
Barriers
Applied accessorylabel to
side of breaker
Bell al arm swit ch ID
Outside auxiliary
switch ID
Inside auxili ary
switch ID
Shunt trip and
Unde rvoltage modu le
Warning:
Danger of electrical shock or injury. Turn off
power supplies ahead of equipment before attempting
to service.
Important::
Danger d’electrocution. Couper
l’alimenation avant d’effectuer toute action d’entretien.
Operate the breaker push to test button and toggle the
handle several times, testing the mechanical operation
of the device. If there are any signs of damage or if the
mechanism is sluggish or sticky, replace the breaker.
For abnormal or heavy duty conditions refer to NEMA
publication AB4 and for recommended maintenance
practices NFPA70B.
G.
Storage
Store in a dry, dust free, environment protected from
corrosion. Long term storage should be in the original
shipping carton. Temperature range –40°C to +80°C.
H.
Accessories
For full details of the accessories and their application,
contact your local
ABB
representatives. When
installing
accessories
r
ead the
accompanying
accessory
installation instruction and
follow carefully
all cautions
and warnings.
®
—
Fig 6. Typical Accessories. See Buylog for Details
4
1SQC930037M0201
,
DEH41
073
February 2020
—
ABB Inc.
305 Gregson Drive
Cary, NC 27511.
electrification.us.abb.com
—
We reserve the right to make technical
changes or modify the contents of this
document without prior notice. With
regard to purchase orders, the agreed
particulars shall prevail. ABB Inc. does not
accept any responsibility whatsoever for
potential errors or possible lack of
information in this document.
We reserve all rights in this document and
in the subject matter and illustrations
contained therein. Any reproduction or
utilization of its contents – in whole or in
parts – is forbidden without prior written
consent of ABB Inc.
Copyright© 2019 ABB
All rights reserved
—
GE is a trademark of GE. Manufactured
by ABB Inc. under license from GE.
If technical assistance is required contact your
local ABB sales office. In the US call ABB Post
Sales Customer Service, 1-888-437-3765.
F. Maintenance
Generally no maintenance is required but it is
recommended that the breaker be cleaned and
inspected on an annual basis.
Note: For a 2 pole breaker there are no auxiliary
switch & bell alarm switch; For a 1 pole there are no
accessories; Installation of an accessory in a 2 pole
breaker is the same as a 3 pole breaker.
These instructions do not cover all details or variations in equipment nor do they provide for every possible contingency that may be met
in connection with installation, operation, or maintenance. Should further information be desired or should particular problems arise that
are not covered sufficiently for the purchaser’s purposes, the matter should be referred to the ABB Company. The breaker is a sealed unit,
which contains no user serviceable parts, tampering with seal will void warranty.