9.1.6
Operation principle
Current circuit supervision CCSRDIF (87) compares the absolute value of the vectorial
sum of the three phase currents |ΣIphase| and the numerical value of the residual current
|Iref| from another current transformer set, see figure
.
The FAIL output will be set to a logical one when the following criteria are fulfilled:
•
The numerical value of the difference |ΣIphase| – |Iref| is higher than 80% of the
numerical value of the sum |ΣIphase| + |Iref|.
•
The numerical value of the current |ΣIphase| – |Iref| is equal to or higher than the set
operate value
IMinOp
.
•
No phase current has exceeded
Pickup_Block
during the last 10 ms.
•
CCSRDIF (87) is enabled by setting
Operation
=
Enabled
.
The FAIL output remains activated 100 ms after the AND-gate resets when being
activated for more than 20 ms. If the FAIL lasts for more than 150 ms an ALARM will be
issued. In this case the FAIL and ALARM will remain activated 1 s after the AND-gate
resets. This prevents unwanted resetting of the blocking function when phase current
supervision element(s) operate, for example, during a fault.
å
II
A
I
ref
å
+
-
å
+
+
I>IMinOp
å
+
-
x
0,8
AND
BLOCK
1,5 x Ir
OR
OPERATION
I>Pickup_Block
FAIL
ALARM
I
ref
BLOCK
OR
I
A
I
B
I
B
I
C
I
C
ANSI11000291-1-en.vsd
0
10 ms
0
20-100 ms
0
150 ms-1 s
ANSI11000291 V1 EN
Figure 87:
Simplified logic diagram for Current circuit supervision CCSRDIF (87)
The operate characteristic is percentage restrained, see figure
.
1MRK 511 287-UUS A
Section 9
Secondary system supervision
205
Technical manual