tDelay: The delay between the UP or DOWN activation signal positive front and the output
activation.
StopAtExtremes: Sets the behavior of the switch at the end positions – if set to Disabled, when
pressing UP while on first position, the switch will jump to the last position; when pressing
DOWN at the last position, the switch will jump to the first position; when set to
Enabled, no
jump will be allowed.
12.6
Selector mini switch VSGAPC
SEMOD158754-1 v3
12.6.1
Identification
SEMOD167850-2 v4
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Selector mini switch
VSGAPC
-
43
12.6.2
Application
SEMOD158803-5 v9
Selector mini switch (VSGAPC) function is a multipurpose function used in the configuration
tool in PCM600 for a variety of applications, as a general purpose switch. VSGAPC can be used
for both acquiring an external switch position (through the IPOS1 and the IPOS2 inputs) and
represent it through the single line diagram symbols (or use it in the configuration through the
outputs POS1 and POS2) as well as, a command function (controlled by the PSTO input), giving
switching commands through the CMDPOS12 and CMDPOS21 outputs.
The output POSITION is an integer output, showing the actual position as an integer number 0
– 3, where 0 = MidPos, 1 = Open, 2 = Closed and 3 = Error.
An example where VSGAPC is configured to switch Autorecloser on–off from a button symbol
on the local HMI is shown in figure
. The I and O buttons on the local HMI are normally used
for on–off operations of the circuit breaker.
IEC07000112-3-en.vsd
PSTO
CMDPOS12
IPOS1
NAM_POS1
NAM_POS2
IPOS2
CMDPOS21
OFF
ON
VSGAPC
SMBRREC
ON
OFF
SETON
INTONE
INVERTER
INPUT
OUT
IEC07000112 V3 EN-US
Figure 186: Control of Autorecloser from local HMI through Selector mini switch
VSGAPC is also provided with IEC 61850 communication so it can be controlled from SA
system as well.
12.6.3
Setting guidelines
SEMOD158807-4 v4
Selector mini switch (VSGAPC) function can generate pulsed or steady commands (by setting
the
Mode parameter). When pulsed commands are generated, the length of the pulse can be
1MRK 505 370-UEN D
Section 12
Control
Busbar protection REB670
331
Application manual
Содержание REB670 Series
Страница 1: ...Relion 670 SERIES Busbar protection REB670 Version 2 2 IEC Application manual ...
Страница 2: ......
Страница 22: ...16 ...
Страница 64: ...58 ...
Страница 226: ...220 ...
Страница 244: ...238 ...
Страница 358: ...352 ...
Страница 392: ...386 ...
Страница 398: ...392 ...
Страница 436: ...430 ...
Страница 454: ...448 ...
Страница 466: ...460 ...
Страница 474: ...468 ...
Страница 475: ...469 ...