![ABB REB650 2.1 IEC Скачать руководство пользователя страница 48](http://html.mh-extra.com/html/abb/reb650-2-1-iec/reb650-2-1-iec_product-manual_4774048.webp)
M12702-1 v4
Table 69. Event recorder
Function
Value
Buffer capacity
Maximum number of events in disturbance report
150
Maximum number of disturbance reports
100
Resolution
1 ms
Accuracy
Depending on time
synchronizing
M13747-1 v5
Table 70. Trip value recorder
Function
Value
Buffer capacity
Maximum number of analog inputs
30
Maximum number of disturbance reports
100
M12384-1 v6.1.1
Table 71. Disturbance recorder
Function
Value
Buffer capacity
Maximum number of analog inputs
40
Maximum number of binary inputs
128
Maximum number of disturbance reports
100
Maximum total recording time (3.4 s recording time and maximum number
of channels, typical value)
340 seconds (100 recordings) at 50 Hz
280 seconds (80 recordings) at 60 Hz
GUID-C43B8654-60FE-4E20-8328-754C238F4AD0 v2
Table 72. Limit counter L4UFCNT
Function
Range or value
Accuracy
Counter value
0-65535
-
Max. count up speed
30 pulses/s (50% duty cycle)
-