ABB REACT-3.6-TL Скачать руководство пользователя страница 3

Application Note| REACT-3.6/4.6-TL – BACKUP OUTPUT|Operation and Configuration  3 

1.

 

Scope and field of application 

 
The REACT system is provided with a source of alternating current (AC) available with an output on a dedicated terminal 
block, capable of feeding household utilities independently on the local power grid. This function is called a “backup”. 
The purpose of this document is to describe the operation and configuration of the backup function available for the 
models listed in the following table: 
 

Models 

REACT-UNO-3.6 -TL (with or without REACT-BATT-AP1) 
REACT-UNO-4.6 -TL (with or without REACT-BATT-AP1) 

  

2.

 

Operation principle 

 

Backup operation is an additional feature provided by the REACT system that allows the inverter to feed household 
utilities independently on the network of the local distributor. The system works based on the typical principle of 
Stand-Alone systems non-connected to the network with, in addition, a backup energy supply due to the presence of 
batteries capable of supporting photovoltaic production to feed the users connected to the line dedicated to the 
backup. 
The backup output can be used to feed loads (that will be defined as “priority loads”) connected either to the home 
network or to the dedicated line, or to feed utilities connected exclusively with the same backup line. 
For a description of the operating principle and referring to the connection layout shown in the figure below, 3 types 
of loads can be identified in a system where the REACT device has been installed, namely: 

 

Priority Loads

: utilities connected exclusively either to the electric system or to the backup line. Priority loads 

will be fed by the local network or by the backup line depending on the configuration of the connection 
circuit and on the type of relay used (see an example in Chapter 6). 

Priority loads will never be fed simultaneously by the backup and the electric system.

 

 

Backup Loads

: these loads are connected exclusively to the backup line, i.e. utilities independent on the local 

electric system. These utilities can be fed only in backup mode, when enabled for operation (e.g. Emergency 
lights). 

 

Grid Loads

: these loads are connected exclusively to the electric system, therefore they are never fed by the 

backup output. 

              

 

Schematic diagram of a household system with backup line  

 

Содержание REACT-3.6-TL

Страница 1: ...Solar Inverters Application Note REACT 3 6 4 6 TL BACKUP OUTPUT USE Operation and Configuration...

Страница 2: ...S 1 Scope and field of application 2 Operation principle 3 General recommendations 4 Specifications 5 Operation modes 5 1 Selecting the mode overview 5 2 Operating conditions 5 3 Mode configuration 5...

Страница 3: ...s connected to the line dedicated to the backup The backup output can be used to feed loads that will be defined as priority loads connected either to the home network or to the dedicated line or to f...

Страница 4: ...ovide power to the utilities connected For safety reasons it is mandatory to appropriately identify the electric sockets connected to the backup line since they could be powered even if there is no ne...

Страница 5: ...below BACKUP OUTPUT Technical Data Rated AC output Voltage Vacr 230 V 1 Maximum output Current Iac max 13 A Rated output Frequency fr 50 Hz Maximum Apparent output Power Sacr 3000 VA Maximum output f...

Страница 6: ...inside the inverter The user designer will select the most appropriate operation mode for the intended use of the system in the house or more generally in the place where the system is installed These...

Страница 7: ...to set the control see section 5 4 2 Manual start press Enter on the display for at least 5 sec This mode may be used whenever condition 1 exists previously established according to a preset control...

Страница 8: ...up operation through manual activation At least one of the following STOP conditions must be met for the backup mode output 1 Press ESC on the display for at least 5 seconds 2 External control signal...

Страница 9: ...Backup operation in the presence of power through manual activation The following STOP conditions must be met for the backup mode output 1 Press ESC on the display for at least 5 seconds Once it has...

Страница 10: ...ltage at the inverter s output terminals and the user decides to feed the loads connected to the backup line Two possible schemes that can be designed and that describe the operation of this mode are...

Страница 11: ...Voltage and Frequency values outside the Mains OK range established according to local standards 2 Control signal from external logic to set the control see section 5 4 3 Manual user activation press...

Страница 12: ...network The external control logic can be associated with the state of the network by closing a NO contact in case of malfunction or absence of power in certain sections of the system or in the entir...

Страница 13: ...exists 1 Power failure at the output terminals of the inverter Voltage and Frequency values outside the Mains OK range established according to local standards If Mode 2 is set the inverter will ente...

Страница 14: ...following STOP conditions must be met for the backup mode output 1 Return of power to inverter terminals Voltage and Frequency values within the Mains OK range established according to local standard...

Страница 15: ...arged beyond the value set Therefore if we assume a 2 kWh battery charge and we set the parameter at 50 in the normal Grid Connected operation the inverter if necessary will draw up to a maximum of 1...

Страница 16: ...ashboard click on REACT Parameters in the Settings menu 2 Select Backup output as the desired mode in the Backup type drop down menu and the residual charge state from the Residual SOC drop down menu...

Страница 17: ...kup line distributor grid connection in every operating condition We recommend using two ABB ESB40 22 230AC DC model contactors with the following simplified electrical diagram As shown in the diagram...

Страница 18: ...tion diagram with Manual 1 Manual 4 and Auto 1 modes In order to ensure the separation of the two power systems backup and mains the connections between the terminals of the contactors must be met as...

Страница 19: ...al ABB representative or visit www abb com solarinverters Copyright 2014 ABB All rights reserved Specifications subject to change without notice Each operation on the REACT 3 6 4 6 TL system shown in...

Отзывы: