Technical data and types: PVS-100 MVCS
Type code (PVS-100-TL-...
Data
2600
2400
2200
2000
1800
1600
1400
1200
1000
800
26
24
22
20
18
16
14
12
10
8
Number of inverters in
parallel
2600
2400
2200
2000
1800
1600
1400
1200
1000
800
Maximum rating in kVA
LV distribution panel
26
24
22
20
18
16
14
12
10
8
Number of fuse protected
feeders
200 A
Fuse rating of feeders
Yes
Breakable on load
Type 2 (type 1 + 2 optional)
Over voltage protection -
replaceable surge arrester
MV transformer
Oil immersed (ONAN)
Transformer type
2600
2400
2200
2000
1800
1600
1400
1200
1000
800
AC power at 30°C in kVA
2600
2400
2200
2000
1800
1600
1400
1200
1000
800
AC power at 40°C in kVA
400 V
Low voltage level
≤ 36 kV
Medium voltage level range
50 Hz or 60 Hz
Rated frequency
Mineral (vegetable optional)
Oil type
± 2 x 2.5%
Tap changer
AI/ AI
Winding material (primary /
secondary)
Yes
Eco efficiency optional
MV switchgear
ABB SafePlus (SF
6
-insulated)
Switchgear type
630 A
Rated current
Single (CV) or double feeder (CCV)
Configuration
Circuit breaker (16 kA or 20 kA / 20 kA or 25 kA)
Protection (up to 24 kV / up
to 36 kV)
ABB REJ603 (others on request)
Protection relay type
Yes
Motorized optional
Auxiliary supply
10 kVA (higher on request)
Auxiliary transformer power
400 / 400-230 V
Auxiliary transformer voltage
Yes
Low voltage distribution
panel for auxiliary functions
Mechanical characteristics
5700 x 2150 x 2500 mm
Length, Width, Height
(L × W × H)
9
9
9
8
8
8
7
7
7
7
Weight approx. ton
Environmental
-25°C … +60°C (with derating above 40 C)
Operating temperature
range
62 Technical data