ABB PVI-3.8/4.6-I-OUTD Скачать руководство пользователя страница 2

12.

Output connection (AC)

14.

Commissioning

15.

Instruments

PVI-3.8_4.6-I-OUTD-Quick Installation Guide EN-RevB

EFFECTIVE 2014-03-13

© Copyright 2014 ABB.  All Rights Reserved.

Specifications subject to change without notice.   

10.

Connection of the communication and control signals

11.

Line cable and protection devices 

 

16.

Structure of the display menu

17.

Characteristics and technical data

9.

Input connection (DC)

13.

Setting the grid standard

Contact us

www.abb.com/solarinverters

LEDs and BUTTONS

, in various combinations, can be used to view the status or carry out complex actions that are described more fully in the manual.

08

07

06

LED

POWER

GREEN

 On if the inverter is working correctly. Flashes when 

checking the grid or if there is insufficient sunlight.

ESC

It is used to access the main menu, to go back to the previous menu 

or to go back to the previous digit to be edited

LED

ALARM

YELLOW

 The inverter has detected an anomaly. The anomaly 

is shown on the display.

UP

It is used to scroll up the menu options or to shift the numerical scale 

in ascending order

LED

GFI

RED 

Ground fault on the DC side of the PV generator. The 

error is shown on the display.

DOWN

It is used to scroll down the menu options or to shift the numerical 

scale in descending order

ENTER

It can be used to confirm an action, to access the submenu for the 

selected option (indicated by the > symbol) or to switch to the next 

digit to be edited

ABB inverters are equipped with a graphic Display 

07

, consisting of 2 lines of 16 characters each, which can be used to:

 -Display the operating state of the inverter and the statistical data

 -Display the service messages for the operator

 -Display the alarm and fault messages for the operator

 -Changing the settings of the inverter

During the normal operation of the inverter the display cycles through the 

GENERAL INFORMATION

. This information relates to the input and output parame-

ters and the inverter identification parameters. By pressing 

ENTER

 it is possible to lock scrolling on a screen to be constantly displayed.

Press 

ESC

 to access the three main menus, which have the following functions:

 

-

STATISTICS:

 

Displays the statistics

 

-

SETTINGS:

  

Modify the settings of the inverter 

 

-

INFO:

 

 

View service messages for the operator

Refer to the manual for details regarding use and functions available in the menu

Check for correct polarity in the input strings and absence of any leakage to ground in the PV generator. When exposed to sunlight, the PV 

panels supply DC direct voltage to the inverter. The inside of the inverter may only be accessed after the equipment has been disconnected 

from the grid and from the photovoltaic generator.

For the string connections it is necessary to use the quick fit connectors (multicontact or weidmüller) located on the bottom of the mechanic 

22

 

23

.

 -

Crimp the Multicontact/Weidmüller MC4/WM4 quick fit connector counterparts (supplied) to the string cables or to the cables wired to the DC disconnect 

switches (external)

 -Connect all the strings included in the design of the system and always check the tightness of the connectors

 -If some of the string inputs should not be used you must proceed to verify the presence of covers on DC input connectors and then install them should they be 

absent: this operation is necessary for the tightness of the inverter and to avoid damaging the free connector that could be used at a later date.

Load protection breaker (AC disconnect switch) and line cable sizing

To protect the AC connection line of the inverter, we recommend installing a device for protection against over current and leakage with the following character-

istics:

PVI-3.8-TL-OUTD

PVI-4.6-TL-OUTD

Type

Automatic circuit breaker with differential thermal magnetic protection

Nominal Voltage / Nominal Current

230 Vac / 20 A

230 Vac / 25 A

Magnetic protection characteristic

B/C

Number of poles

2

Type of differential protection

A/AC

Differential sensitivity

30 mA

ABB declares that the ABB transformerless inverters, in terms of their construction, do not inject continuous ground fault currents and therefore there is no requirement 

that the differential protection installed downstream of the inverter be type B in accordance with IEC 60755 / A 2.

Characteristics and sizing of the line cable

Three-pole cable required. The cross-section of the AC line conductor must be sized in order to prevent unwanted disconnections of the inverter from the grid 

due to high impedance of the line that connects the inverter to the power supply point.

Cross-section of the line conductor (mm

2

)

Maximum length of the line conductor (mt)

PVI-3.8-I-OUTD

PVI-4.6-I-OUTD

4 mm²

15 m

11 m

6 mm²

23 m

16 m

10 mm²

40 m

28 m

16 mm²

64 m

45 m

The values are calculated in nominal power conditions, taking into account: 

1. a power loss of not more than 1% along the line.    2. copper cable, with HEPR rubber insulation, laid in free air

  max 16 mm²

13 ÷ 21 mm

Each cable which must be connected to the connectors of the communication and control signals must pass through one of the two service cable glands 

25

.

An M20 cable gland (that takes cables from 7 mm to 13 mm in diameter) and a gasket with two holes to insert into the cable gland which enables two separate 

cables of a maximum diameter of 5 mm to be accommodated, are available.

Warning! To ensure environmental protection IP65 it is necessary to fix the cable glands to the inverter chassis with a minimum tightening 

torque of 7 Nm

Connection to the RS485 communication line

The RS485 communication port is the inverter’s communication port. The ABB inverters use 

an RS485 HALF-DUPLEX communication line made up of two transmission and reception 

cables (+T/R and –T/R) and a communication reference cable (RTN): all three cables must be 

connected in daisy-chain configuration. The chain connection can be made without distinction 

by using the RJ45 connector couples 

15

 (one for in and one for out) or the terminal block 

20

.The last inverter in the daisy chain must be “terminated” or the 120 Ohm communication line 

termination resistance must be activated by switching the dip-switch 

14

.

Using the alarm terminal block

Terminal block 

19

 connecting to the configurable relay that allows connection of external 

devices which, according to the mode selected in the menu “

SETTINGS > Alarm

” can, for 

example, signal malfunctions. The operating modes that can be set are: Production and Alarm.

The ALARM contact can be used only with systems that ensure a safety isolating additional at least (supplementary insulation in relation to 

the DC input voltage)

Using the REM terminal block

The REM terminal block 

20

, if suitably configured, allows the “Remote ON/OFF” function to be used: this function allows remote disconnection of the inverter 

from the grid

For further information regarding the configuration and use of the communication and control signals terminal block, please see the manual

16

20

19

13

15

The inverter commissioning procedure is as follows:

 -Switch the integrated switch 

21

 (version –S) to the ON position or close the external switches: If the input voltage applied to one of the two input channels is 

greater than the minimum starting voltage, the inverter will start up.

 -

The message “Initializing...Please Wait” will be displayed; Depending on the input voltage value, the inverter will show various messages on the display and 

change the behaviour of the three LED 

06

:

INPUT VOLTAGE

DISPLAY MESSAGE

LED STATUS

DESCRIPTION

Vin < Vstart

Waiting Sun

Green  = FLASHING

Yellow = OFF

Red      = OFF

The input voltage is not sufficient to permit connection to the grid.

Vin > Vstart

Missing Grid

Green  = FLASHING

Yellow = ON

Red      = OFF

There is sufficient input voltage to permit connection to the grid: the in

-

verter waits until there is grid voltage to carry out the parallel connection.

The inverter is powered ONLY by the voltage coming from the photovoltaic generator: presence of grid voltage alone IS NOT SUFFICIENT to permit 

the inverter to start up.

 -With the inverter in “Missing Grid” status, close the AC switch downstream the inverter so as to supply the grid voltage to the inverter: the inverter performs 

the grid voltage check, measures the photovoltaic generator insulation resistance against earth and carries out other self-diagnosis checks. During the 

checks before the parallel with the grid, the green LED keeps flashing, the others are off.

During the grid voltage check and measurement of the insulation resistance, the values for the grid voltage and frequency and the insulation 

resistance measured by the inverter are shown on the display. The inverter ONLY creates a parallel with the grid if the grid parameters fall within the 

range foreseen by current regulations and if the insulation resistance falls within the set parameters.

 -If the preliminary checks for parallel connection to the grid are successful, the inverter connects to the grid and begins to export power to the grid. At this 

stage, the display shows the inverter’s parameters in cycles. The green LED stays lit whereas the others are off.

Before connecting the inverter to the distribution grid it is necessary to set the country standard by manipulating the two rotary switches 

12

.

Note: The settings become fixed after 24 hours of operation of the inverter (the PV generator simply has to be under power).

Switch

Country Grid Standard

(name displayed)

Display 

language

Switch

Country Grid Standard

(name displayed)

Display 

language

1

2

1

2

0

0

NON-ASSIGNED

ENGLISH

1

F

BRAZIL @ 220V (

BRAZIL

)

ENGLISH

0

1 GERMANY VDE 0126 @ 230V Single Phase (

VDE 0126

)

ENGLISH

2

0

CLC/FprTS 50549 (

TURKEY LV

)

ENGLISH

0

5

ENEL GUIDA @ 230V Single Phase (

ENEL

)

ENGLISH

2

1

ANRE no.30/17.V.2013 (

ROMANIA

)

ENGLISH

0

6

SPAIN RD 1699 @ 230V (

RD 1699

)

SPANISH

2

2

Slovenian (

SLOVENIA

)

ENGLISH

0

7

UK – G83 @ 230V (

UK G83

)

ENGLISH

2

3

CLC/FprTS 50549 (

TURKEY HV

)

ENGLISH

0

8

UK – G59 @ 230V (

UK G59

)

ENGLISH

0 1 2

 3 4

 5 6 7 

8 9 A

 B

 C

 D E

 F

2

1

0 1 2

 3 4

 5 6 7 

8 9 A

 B

 C

 D E

 F

0

9

IRELAND @ 230V (

IRELAND

)

ENGLISH

0

A

AUSTRALIA @ 230V (

AS 4777

)

ENGLISH

0

D

FRANCE @ 230V (

FRANCE

)

FRENCH

0

E

NETHERLANDS @ 230V (

NETHERL

)

ENGLISH

0

F

GREECE @ 230V (

GREECE

)

ENGLISH

1

0

PORTUGAL @ 230V (

PORTUGAL

)

ENGLISH

1

1

CORSICA @ 230V (

CORSICA

)

FRENCH

1

2

HUNGARY @ 230V (

HUNGARY

)

ENGLISH

1

6

CHECA REPUBLIC @ 230V (

CZECH

)

CZECH

1

7

GERMANY–VDE AR-N-4105 @230V (

VDE 4105

)

GERMAN

1

8

CEI-021 @ 230V INTERNAL Protection (

CEI021 IN

)

ITALIAN

1

9

CEI-021 @ 230V EXTERNAL Protection (

CEI021 EX

)

ITALIAN

1

D

BELG C10-11 100% @ 230V (

C1011 100

)

FRENCH

1

E

BELG C10-11 110% @ 230V (

C1011 110

)

FRENCH

The list of grid standards given in the table was valid at the time of issue of the manual. It will be continually updated as new country standards 

with which the inverter is compatible are introduced

Warning! Before performing any of the operations described below, ensure the AC line downstream the 

inverter has been correctly disconnected

 -

Remove the protective film located on the hole to be used for the AC cables 

24

 -Insert the M32 cable gland in the hole and secure it using the special M32 lock nut (supplied)

Warning! To ensure environmental protection IP65 it is necessary to fix the cable gland to the inverter 

chassis with a minimum tightening torque of 8.0 Nm

 -Strip 10 mm of sheathing from the AC grid connection cables

 -Plug the AC line cable into the inverter, passing it through the previously installed cable gland

 -Connect the protective earth (yellow-green) cable to the contact labelled with the 

 symbol on the terminal block 

18

Warning! ABB inverters should be earthed (PE) via the terminal with the protective earth label  , using a cable with an appropriate cross-

section of the conductor for the maximum ground fault current that the generating system might experience

 -Connect the neutral cable (normally blue) to the terminal labelled with the letter 

N

 -Connect the phase cable to the terminal labelled with the letter 

L

Warning! The AC cables must be tightened on the terminal block with a minimum torque of 1.5 Nm

Once the connection to the terminal board 

18

 is complete, screw in the cable gland firmly (tightening torque 5.0Nm) and check the tightness.

18

PVI-3.8-I-OUTD

PVI-4.6-I-OUTD

Input

Absolute Maximum Input Voltage (V

max,abs

)

520 V

Input Activation Voltage (V

start

)

200 V (adj. 120...350 V)

Input Operating Range (V

dcmin

...V

dcmax

)

0.7 x Vstart...520 V

Rated DC Input Power (P

dcr

)

4000 Wp

4800 Wp

Number of Independent MPPTs 

(6)

Maximum Input Power for each MPPT (P

MPPT max

)

3000 W

MPPT Input DC Voltage Range (V

MPPT min

,f ... V

MPPT max

,f) at P

acr

160...470 V

180...470 V

Maximum DC Input Current (I

dc max

) / for each MPPT (I

MPPT max

)

25.0 A / 12.5 A

28.0 A / 14.0 A

Maximum Input Short Circuit Current for each MPPT

22.0 A

Maximum Backfeed current (from AC to DC side)

Negligible

Number of DC Inputs Pairs for each MPPT

2

DC Connection Type

Connettore PV Tool Free WM / MC4

Input protection

Reverse Polarity Protection

Yes, from limited current source

Input Overvoltage Protection for each MPPT - Varistor

2

Photovoltaic Array Isolation Control

According to local standard

DC Switch Rating (-S Version)

Max. 25.0 A / 600 V

Output

AC Grid Connection Type

Monophase

Rated AC Power (P

acr

)

3800 W

4600 W

Maximum AC Output Power (P

ac max

)

4200 W 

(1)

5000 W 

(2)

Rated AC Grid Voltage (V

acr

)

230 V

AC Voltage Range

180...264 Vac 

(4)

Maximum AC Output Current (I

ac max

)

18.2 A 

(3)

22.5 A

Inrush Current

Negligible

Maximum Output Fault Current

<25Arms (100mS)

Rated Output Frequency (f

r

)

50 Hz / 60 Hz

Output Frequency Range (f

min

...f

max

)

47...53 / 57...63 Hz 

(5)

Nominal Power Factor (Cosphi

acr

)

>0.995 adj. ± 0.9 with Pacr= 3.8 kW

>0.995 adj. ± 0.9 with Pacr= 4.6 kW

Total Harmonic Distortion of Current 

< 2%

AC Connection Type

Screw terminal block

Output protection

Anti-Islanding Protection

According to local standard

Maximum AC Overcurrent Protection

20.0 A

25.0 A

Output Overvoltage Protection - Varistor

2 (L - N / L - PE)

Operating performance

Maximum Efficiency (η

max

)

96.8%

Weighted Efficiency (EURO/CEC)

96.5% / -

Power Input Treshold

24.0 W

Stand-by Consumption

< 8.0 W

Communication

Wired Local Monitoring

PVI-USB-RS232_485 (opz.), PVI-DESKTOP (opz.)

Remote Monitoring

PVI-AEC-EVO (opz.), VSN700 Data Logger (opz.)

Wireless Local Monitoring

PVI-DESKTOP (opz.) with PVI-RADIOMODULE (opz.)

User Interface

LCD Display with 16 characters x 2 line

Environmental

Ambient Temperature Range

-25...+60°C /-13...140°F

-25...+60°C /-13...140°F 

with derating above 50°C/122°F

Storage Temperature

-40...80°C (-40...+176°F)

Relative Humidity

0...100% condensing

Environmental pollution classification for external environment

3

Noise Emission

< 50 dB(A) @ 1 m

Maximum Operating Altitude without Derating

2000 m / 6560 ft

Environmental Category

External

Physical

Environmental Protection Rating

IP 65

Cooling

Natural

Dimension (H x W x D)

712 x 325 x 222 mm    /    28.0 x 12.8 x 8.7 inch

Weight

< 24.0 kg / 53.0 lb

Mounting System

Wall bracket

Overvoltage Category in accordance with IEC 62109-1

II (DC input)    III (AC output)

Safety

Isolation Level

HF transformer

Safety Class

I

Marking

CE (50Hz only)

1. Limited to 3800 W for Germany

2. Limited to 4600 W for Germany

3. Limited to 16 A for UK G83/1 standard

4. The AC voltage range may vary depending on specific country grid standard

5. The Frequency range may vary depending on specific country grid standard

6. Independent MPPT only available with negative input grounded.

Remark. Features not specifically listed in the present data sheet are not included in the product