background image

11.

Connection of the communication and control signals

12.

Commissioning

PVI-3.0_3.6_4.2-TL-OUTD-W-Quick Installation Guide EN-RevA

EFFECTIVE 2014-04-02

© Copyright 2014 ABB.  All Rights Reserved.

Speciications subject to change without notice.   

9.

Line cable and protection devices 

 

10.

Output connection (AC)

14.

Instruments

15.

Characteristics and technical data

Coniguration parameter of power curve

13.

Load protection breaker (AC disconnect switch) and line cable sizing

To protect the AC connection line of the inverter, we recommend installing a device for protection against over current and leakage with the following characteristics:

PVI-3.0-TL-OUTD-W

PVI-3.6-TL-OUTD-W

PVI-4.2-TL-OUTD-W

Type

Automatic circuit breaker with differential thermal magnetic protection

Nominal Voltage

230 Vac

Nominal Current

20 A

25 A

Magnetic protection characteristic

B/C

Number of poles

2

Type of differential protection

A/AC

Differential sensitivity

300 mA

ABB declares that the ABB transformerless inverters, in terms of their construction, do not inject continuous ground fault currents and therefore there is no 

requirement that the differential protection installed downstream of the inverter be type B in accordance with IEC 60755 / A 2.

Characteristics and sizing of the line cable

Three-pole cable required. The cross-section of the AC line conductor must be sized in order to prevent unwanted disconnections of the inverter from the grid 

due to high impedance of the line that connects the inverter to the power supply point.

Cross-section of the line conductor (mm

2

)

Maximum length of the line conductor (mt)

PVI-3.0-TL-OUTD-W

PVI-3.6-TL-OUTD-W

PVI-4.2-TL-OUTD-W

4 mm²

19 m

16 m

14 m

6 mm²

29 m

24 m

21 m

10 mm²

48 m

41 m

35 m

16 mm²

77 m

65 m

56 m

The values are calculated in nominal power conditions, taking into account: 1. a power loss of not more than 1% along the line.    2. copper cable, with HEPR rubber insulation, laid in free air

Contact us

www.abb.com/converters-inverters

  max 16 mm²

~13÷21 mm

Warning! Before performing any of the operations described below, ensure the AC line downstream the 

inverter has been correctly disconnected

 

- Remove the protective cap on the hole 

19

 used to pass the AC cable into the inverter.

 

-

Insert an M32 cable gland (or compatible - hole diameter 33.8 mm) in the hole to be used for the AC output cable 

19

Warning! To ensure environmental protection IP65 it is necessary to ix the cable gland to the inverter 

chassis with the minimum tightening torque speciied in the cable gland manufacturer’s datasheet.

 

- Strip 10 mm of sheathing from the AC grid connection cables

 

- Plug the AC line cable into the inverter, passing it through the previously installed cable gland

 

- Connect the protective earth (yellow-green) cable to the contact labelled with the 

 symbol on the terminal block 

10

Warning! ABB inverters should be earthed (PE) via the terminal with the protective earth label  , using a cable with an appropriate cross-

section of the conductor for the maximum ground fault current that the generating system might experience

 

- Connect the neutral cable (normally blue) to the terminal labelled with the letter 

N

 

- Connect the phase cable to the terminal labelled with the letter 

L

Warning! The AC cables must be tightened on the terminal block with a minimum torque of 1.5 Nm

Once the connection to the terminal board 

10

 is complete, screw in the cable gland irmly and check the tightness.

10

Each cable which must be connected to the connectors of the communication and control signals must pass through one of the two service cable glands 

20

.

An M20 cable gland (or compatible – hole diameter 20.3 mm) must be inserted in one of two of the service cable glands holes 

20

.

Warning! To ensure environmental protection IP65 it is necessary to ix the cable gland to the inverter chassis with the minimum tighte-

ning torque speciied in the cable gland manufacturer’s datasheet.

Connection of the tachometer signal

The tachometer signal allows the 7200-WIND-INTERFACE-EU to drive the inver-
ter. It is therefore necessary to connect up the two cables from the 7200-WIND-
INTERFACE-EU (

WIND SPEED+

 and 

WIND SPEED-

) to the tachometer signal 

terminal block 

13

 in correspondence with terminals 

+WT

 and 

-WT

.

Connection to the RS485 communication line

The RS485 communication line (identiied by the pair of connectors RJ45 

14

 and by the terminal block 

13

) must necessarily be connected to the 

7200-WIND-INTERFACE-EU. For further details on connection of the RS485 
line please see the 7200-WIND-INTERFACE-EU manual.

Using the ALARM terminal block

Terminal block 

13

 connecting to the conigurable relay that allows connection 

of external devices which, according to the mode selected in the menu “

SET

-

TINGS > Alarm

” can, for example, signal malfunctions. The operating modes 

that can be set are: Production and Alarm.

14

15

13

The ALARM contact can be used only with systems that ensure a safety isolating additional at least (supplementary insulation in relation 

to the DC input voltage)

Using the REM terminal block

The REM terminal block 

13

, if suitably conigured, allows the “Remote ON/OFF” function to be used: this function allows remote disconnection of the inverter from the grid

For further information regarding the coniguration and use of the communication and control signals terminal block, please see the 

manual

The inverter commissioning procedure is as follows:

 

- Close the external switches: If the input voltage is greater than the minimum starting voltage, the inverter will start up.

 

-

When the inverter is turned on for the irst time you will be asked to select the “Nation” of installation. This selection allows the inverter to automatically coni

-

gure its parameters to ensure that compliance with local standards; the default language corresponding to the selected “Nation” will also be set.

Warning! After the grid standard was set you have 24 hours to make any changes to the grid standard value; 24 hours later the “Nation 

Select.” functionality will be blocked, and any subsequent changes can only be made using a password provided on request by ABB

Loading the Power Curve of eolic generator

After you have set the “Nation” value, the error message “W009 Empty Table” will be displayed. This message indicates that the wind turbine power curve has 

not yet been loaded into the inverter. Thus, before connecting the inverter into the power grid, you must load the curve using the Aurora Installer software. 
Follow the following step-by-step procedure for upload the power curve:

 

-

Inverters can use a power curve deined either in terms of the input voltage to the inverter (P(Vin)) or as a function of the wind turbine frequency (P(f)). Where 

a frequency power curve has been chosen (P(f)), ensure that the tachymetric signal has been correctly connected.

 

- Install the Aurora Installer application on your PC

 

-

Supply a limited input voltage to the inverter which is just suficient to start up the inverter (50V / 1A). The wind turbine itself can be used to supply this 

voltage, provided it can produce at least 50V

 

- Connect the inverter to your PC using the PVI-USB-RS485_232 converter (for details of the connection, see the PVI-USB-RS485_232 converter manual)

 

- Launch the Aurora Installer application

1.  In the 

“Conigu-

ration”

 window select 

the COM port from the 
pull-down menu, enter 
the number of inverters 
you have connected to 
the PC and click OK.

2.  The application will 
scan the communica-
tion line looking for the 
connected inverters. The 
discovered inverters will 
be displayed in a table. 
Click 

“-->”

 to select the 

inverter you want to 
work with.

3.  In the 

“Mode Se-

lection”

 window select 

“Extended”

 and enter 

the following password: 

05591

. Then click OK.

4.  Go to the 

“Wind 

Coniguration”

 tab: the 

application will read the 
power curve table in the 
inverter (this will happen 
even if no table has yet 
been loaded, in which 
case no curve will be 
shown in the graph);

5.   From 

“Online”

 mode 

go to 

“Edit”

 mode to 

compile the power curve 

(see the “Parameters” ta

-

ble for information about 
compiling the power 
curve) Alternatively, to 

load a ile in .mpp format 

created previously, click 

“File”

 and select the 

.mpp ile to load.

6.  From 

“Edit”

 mode go to 

“On Line”

 mode again and click 

“Send”

 to send the table to the 

inverter.

Note: If you want to apply the 

same curve to more than one 

inverter, click “File” and “Save 

As” to export the curve to your 
PC in .mpp format so that it is 
available for other inverters.

The following parameters must be provided, with the power curve, by turbine’s manufacturer. See table below for more details about the parameters:

PARAMETERS

Output Power Ramp
(Pout Ramp)

This is the response speed of the inverter, i.e. how quickly the take-off point of the inverter follows the take-off point of the turbine. 

The value must be between 275 W/sec and 10,000 W/sec. In the commissioning phase of the system, if an instability is detected, try 

reducing the “Pout Ramp” value.

Inverter Activation 
Voltage (Vin Start)

This is the input voltage above which the inverter connects to the grid. The value must be between 50V and 200V.

Undervoltage 
protection time 
(Tprot UV)

This is the length of time the inverter remains switched on after the voltage has dropped below the “Vin Start” value. This parameter 

allows you to keep the inverter connected to the grid even if the input voltage drops below ”Vin Start”. It can then start exporting ener

-

gy again to the grid whenever the wind pickups, without having to repeat the inverter start-up process. The value must be between 1 
sec and 3600 sec.

Nominal Grid Voltage 
(Vgrid Nom)

Indicates the rated voltage of the grid to which the inverter is connected.

 

-

After having loaded the wind turbine power curve, the message “Inizializing...Please Wait” is displayed. Depending on the input voltage value, the inverter will 

show various messages on the display and change the behaviour of the three LED 

06

:

INPUT VOLTAGE

DISPLAY MESSAGE

LED STATUS

DESCRIPTION

Vin < Vstart

Waiting Wind

Green  = FLASHING
Yellow = OFF
Red      = OFF

The input voltage is not suficient to permit connection to the grid.

Vin > Vstart

Missing Grid

Green  = FLASHING
Yellow = ON
Red      = OFF

There is suficient input voltage to permit connection to the grid: 

the inverter waits until there is grid voltage to carry out the parallel 
connection.

The inverter is powered ONLY by the voltage coming from the wind power system: presence of grid voltage alone IS NOT SUFFICIENT to permit the 

inverter to start up.

 

-

With the inverter in “Missing Grid” status, close the AC switch downstream the inverter so as to supply the grid voltage to the inverter: the inverter performs the 

grid voltage check, measures the wind power system insulation resistance against earth and carries out other self-diagnosis checks. During the checks before 

the parallel with the grid, the green LED keeps lashing, the others are off.

During the grid voltage check and measurement of the insulation resistance, the values for the grid voltage and frequency and the insulation resi

-

stance measured by the inverter are shown on the display. The inverter completes parallel connection with the grid SOLELY if the grid parameters 

meet the ranges provided for by the regulations in force and if the insulation resistance is greater than 1Mohm.

 

- If the preliminary checks for parallel connection to the grid are successful, the inverter connects to the grid and begins to export power to the grid. At this stage, 

the display shows the inverter’s parameters in cycles. The green LED stays lit whereas the others are off.

LEDs and BUTTONS

, in various combinations, can be used to view the status or carry out complex actions that are described more fully in the manual.

08

07

06

LED

POWER

GREEN

 On if the inverter is working correctly. Flashes when 

checking the grid or if there is insuficient wind.

ESC

It is used to access the main menu, to go back to the previous menu 
or to go back to the previous digit to be edited

LED

ALARM

YELLOW

 The inverter has detected an anomaly. The anomaly 

is shown on the display.

UP

It is used to scroll up the menu options or to shift the numerical scale 
in ascending order

LED
GFI

RED 

Ground fault on the DC side of the PV generator. The 

error is shown on the display.

DOWN

It is used to scroll down the menu options or to shift the numerical 
scale in descending order

ENTER

It can be used to conirm an action, to access the submenu for the 

selected option (indicated by the > symbol) or to switch to the next 
digit to be edited

PVI-3.0-TL-OUTD-W

PVI-3.6-TL-OUTD-W

PVI-4.2-TL-OUTD-W

Input
Absolute Maximum Input Voltage (V

max,abs

)

600 V

Input Activation Voltage (V

start

)

50 V (adj. 50...350 V)

Input Operating Range (V

dcmin

...V

dcmax

)

50...580 V

Input DC Voltage Range (V

min

,f ... V

max

,f) at P

acr

160...530 V

120...530 V

140...530 V

Maximum DC Input Current (I

dc max

)

20.0 A

32.0 A

32.0 A

Maximum Input Short Circuit Current

25 A

40.0 A

40.0 A

Maximum Backfeed current (from AC to DC side)

Negligible

DC Connection Type

Screw terminal block

Input protection
Reverse Polarity Protection

Yes, from limited current source

Input Overvoltage Protection - Varistor

2

Photovoltaic Array Isolation Control

According to local standard

Output
AC Grid Connection Type

Monophase

Rated AC Power (P

acr

)

3000 W

3600 W

4200 W

Maximum AC Output Power (P

ac max

)

3300 W 

(1)

4000 W 

(2)

4600 W 

(3)

Rated AC Grid Voltage (V

acr

)

230 V

AC Voltage Range

180...264 Vac 

(4)

Maximum AC Output Current (I

ac max

)

14.5 A

17.2 A 

(5)

20.0 A

Inrush Current

Negligible

Maximum Output Fault Current

<25 A rms (100mS)

Rated Output Frequency (f

r

)

50 Hz

Output Frequency Range (f

min

...f

max

)

47...53 / 57...63 Hz 

(6)

Nominal Power Factor (Cosphi

acr

)

>0.995 adj. ± 0.9 with Pacr= 

3.0 kW

>0.995 adj. ± 0.9 with Pacr= 

3.6 kW

>0.995 adj. ± 0.9 with Pacr= 

4.2 kW

Total Harmonic Distortion of Current 

< 3.5%

AC Connection Type

Screw terminal block

Output protection
Anti-Islanding Protection

According to local standard

Maximum AC Overcurrent Protection

16.0 A

19.0 A

22.0 A

Output Overvoltage Protection - Varistor

2 (L - N / L - PE)

Operating performance

Maximum Eficiency (η

max

)

96.8%

Power Input Treshold

10.0 W

Stand-by Consumption

< 8.0 W

Communication
Wired Local Monitoring

PVI-USB-RS232_485 (opt.)

Remote Monitoring

WIFI LOGGER CARD (opt.), PVI-AEC-EVO (opt.), VSN700 Data Logger (opt.)

Wireless Local Monitoring

WIFI LOGGER CARD (opt.)

User Interface

LCD Display with 16 characters x 2 line

Environmental
Ambient Temperature Range

-25...+60°C /-13...140°F with 

derating above 50°C/122°F

-25...+60°C /-13...140°F with 

derating above 55°C/131°F

-25...+60°C /-13...140°F with 

derating above 50°C/122°F

Storage Temperature

-40...80°C (-40...+176°F)

Relative Humidity

0...100% condensing

Environmental pollution classiication for external environment

3

Noise Emission

< 50 dB(A) @ 1 m

Maximum Operating Altitude without Derating

2000 m / 6560 ft

Environmental Category

External

Physical
Environmental Protection Rating

IP 65

Cooling

Natural

Dimension (H x W x D)

618 x 325 x 222 mm    /    24.3 x 12.8 x 8.7 inch

Weight

17.5 kg / 38.6 lb

Mounting System

Wall bracket

Overvoltage Category in accordance with IEC 62109-1

II (DC input)    III (AC output)

Safety
Isolation Level

Transformerless (TL)

Safety Class

I

Marking

CE (50Hz only)

1. Limited to 3000 W for Germany
2. Limited to 3600 W for Germany
3. Limited to 4200 W for Germany

4. The AC voltage range may vary depending on speciic country grid standard

5. Restricted to 16 A (up to the maximum output power of 3680 W) for the standard UK G83/1.

6. The Frequency range may vary depending on speciic country grid standard

Remark. Features not speciically listed in the present data sheet are not included in the product

Отзывы: