![ABB PSTX370 Скачать руководство пользователя страница 19](http://html1.mh-extra.com/html/abb/pstx370/pstx370_service-manual_4097806019.webp)
1SFC13105M0201 | Service Manual |
Service PSTX210...370
19
3.2
Configuring the HMI
This chapter describes how update firmware, set the ID
and how to reset the Softstarter to default.
3.2.1
Update Firmware
Firmware needs to be updated when changing the HMI.
Please contact your ABB sales office for information.
See Figure 1.
3.2.2
Set the ID
The ID of the Softstarter has to be changed when the
PCBA has been changed and after updating firmware.
Choose between 210…370 due to type of Softstarter.
1.
Switch on the power supply (terminal 1 and 2).
2.
1
Push
”Menu” to reach Menu.
Use
or
to navigate to
Parameters
and then
push
”Select”.
3.
2
Use
or
to navigate to
Complete list
and then push
”Select”.
4.
3
Use
or
to navigate to
28
Service
and
then push
”Select”.
5.
4
Use
or
to navigate to
28.01
ID
and then
push
”Edit”.
6.
5
Use
,
to set
28.01
ID
to
105
and then push
”Save”.
1
3.2.2_3
1
2
3
4
5
3
Содержание PSTX370
Страница 1: ...Softstarter type PSTX210 370 and PSTX470 570 Service manual Service manual en rev A 1SFC13105M0201 ...
Страница 4: ......
Страница 6: ......
Страница 13: ...1SFC13105M0201 Service Manual Description 13 2 ...
Страница 16: ...16 Description Service Manual 1SFC13105M0201 2 ...
Страница 43: ...1SFC13105M0201 Service Manual Service PSTX210 370 43 3 ...
Страница 44: ...44 Service PSTX210 370 Service Manual 1SFC13105M0201 3 ...
Страница 80: ...80 Service PSTX470 570 Service Manual 1SFC13105M0201 4 ...
Страница 83: ...1SFC13105M0201 Service Manual Wiring Diagrams 83 5 ...
Страница 85: ...1SFC13105M0201 Service Manual Revisions 85 6 ...